Approved Venting Materials; Vent Term Ination - UTICA BOILERS MAHF-75 Installation, Operation And Maintenance Manual

Condensing gas fired boiler
Table of Contents

Advertisement

!
W ARN I N G
Manufact urer recom m ends t his condensing boiler
be vent ed wit h approved polypropylene vent ing
m at erial. Use only m at erials list ed below for
vent pipe, intake air pipe, and fittings. Failure to
com ply could result in deat h or serious inj ury.
!
W ARN I N G
• Covering non-metallic vent pipe and fittings
wit h t herm al insulat ion shall be prohibit ed.
• Use of cellular core PVC for venting flue gas
could result in deat h, or serious inj ury.
• Coaxial vent ing shall be fast ened wit h screws.
Dual flue venting is NOT fastened with screws.
!
W ARN I N G
Do not use cellular core pipe. Only specified
sized pipes are t o be used. When using vent ing
m at erial ot her t han boiler m anufact urer's
vent ing, not e t he correct inst allat ion procedure.
Failure t o follow t hese inst ruct ions could result in
deat h, or serious inj ury.
!
W ARN I N G
Asphyxiat ion hazard! Pipe out door com bust ion
air direct ly t o boiler air connect ion. Ensure
com bust ion air does not cont ain cont am inant s
and is not drawn from an area likely t o have
cont am inant s. For exam ple, never pipe
com bust ion air from areas near swim m ing pools
or laundry room exhaust vent s. Cont am inat ed
com bust ion air will dam age boiler result ing in
deat h or serious inj ury.
5 - COM BU STI ON AI R AN D V EN T PI PI N G
5 .4 Approved Vent ing M a t eria ls
I nst allat ion shall conform t o requirem ent s of aut horit y
having j urisdict ion or in absence of such requirem ent s:
• USA - Nat ional Fuel Gas Code, ANSI Z223.1/ NFPA
54.
• Canada - Nat ural Gas and Propane I nst allat ion Code,
CAN/ CSA B149.1
1.
Vent ing shall be properly support ed.
2.
Boiler shall not support any t ype of vent syst em .
All piping, glue, solvents, cleaners, fittings and
3.
com ponent s m ust conform t o ASTM and ANSI
st andards. I n Canada ULC S636 and in t he USA UL
1738 schedule 40 CPVC are t he only approved vent
syst em t o be used as an alt ernat ive t o polypropylene
vent ing for t he exhaust pipe.
4.
Manufact urer requires use of a m echanical fast ener
at every push-fit gasket connection when using a
single wall polypropylene vent syst em .
5 .5 Vent Term ina t ion
• Terminate combustion air and vent pipes with fittings
or coaxial vent kit . Refer t o vent ing illust rat ions for
det ails.
• Separat e vent t erm inal from air inlet t erm inal t o
prevent flue gas recirculation. If T-Terminal is used
on flue pipe at sidewall, air inlet terminal shall be at
least 36" or m ore away from vent t erm inal.
• Locat e com bust ion air t erm inat ion as far as possible
from swim m ing pool, swim m ing pool pum p house,
and ot her sources of airborne chlorine.
• Locat e com bust ion air and vent t erm inals as required
by aut horit y having j urisdict ion.
Approved Polypropylene M a nufa ct urers
* Nat alini
®
* DuraVent
* Cent rot herm
®
* Z- Flex
Not e: Maxim um equivalent lengt h m ay vary bet ween
m anufact urers.
1 9
240013503 REV A, [ 03/ 15/ 2022]