TABLE OF CONTENTS Verify Contents Received ..........2 9 - Start Up Procedure ..........47 9.1 Central Heating System Connections - Heat Only .. Table Of Contents ............3 9.2 Central Heating System Connections - Combi ..Physical Data..............4 9.3 System Start Up ...........49 1 - Important Information ..........6 9.4 Fill Condensate Trap With Water ......49 9.5 Control Panel ............50...
1 - IMPORTANT INFORMATION 1. Safety Information FOR YOUR SAFETY READ BEFORE OPERATING Boiler installation shall be completed by qualified agency. See DANGER glossary for additional information. WARNING Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury.
• Exceed 176°F (80°C) system design temperature. Additional manual reset low water cutoff may be required. 2.7 Operational Features 2.3 Requirements for Commonwealth of • MAH-100 Modulates input to provide CH Turndown Massachusetts: 5.6:1 Boiler installation must conform to Commonwealth of •...
3 - COMPONENT LISTING UTICA BOILER MAH-100 Exhaust Port Intake Port Utica Boiler ITEM MAH-100 Pump with Air Separator Boiler Drain Tap Gas Valve Low Water Pressure Cutoff 3-Way Valve with Motor Water Safety Thermostat NTC Heating sensor (Flow/Return) QTY 2, (1 Shown for clarity)
Page 13
3 - COMPONENT LISTING UTICA BOILER MAH-125 Exhaust Port Intake Port Utica Boiler ITEM MAH-125 Pump with Air Separator Boiler Drain Tap Gas Valve Low Water Pressure Cutoff 3-Way Valve with Motor Water Safety Thermostat NTC Heating sensor (Flow/Return) QTY 2, (1 Shown for clarity) Flue Sensor Pressure Switch Coaxial Flue Connector...
Page 14
3 - COMPONENT LISTING UTICA BOILER MAH-165 Exhaust Port Intake Port Utica Boiler ITEM MAH-165 Pump Boiler Drain Tap Low Water Pressure Cutoff Gas Valve NTC Heating sensor (Flow/Return) QTY 2, (1 Shown for clarity) Water Safety Thermostat Flue Sensor Coaxial Connector Heat Exchanger Temperature Protector...
Page 15
3 - COMPONENT LISTING UTICA BOILER MAC-115 Exhaust Port Intake Port Utica Boiler ITEM MAC 115 Pump with Air Separator Boiler Drain Tap Flow Sensor with Water Filter and Flow Restrictor DHW Priority Sensor Controlled Fast Fill Gas Valve NTC DHW Sensor Low Water Pressure Cutoff 3-Way Valve with Motor Check Valve...
Page 16
3 - COMPONENT LISTING UTICA BOILER MAC-150 Exhaust Port Intake Port Utica Boiler ITEM MAC- 150 Pump with Air Separator Boiler Drain Tap Flow Sensor with Water Filter and Flow Restrictor DHW Priority Sensor Controlled Fast Fill Gas Valve NTC DHW Sensor Low Water Pressure Cutoff 3-Way Valve with Motor Check Valve...
Page 17
3 - COMPONENT LISTING UTICA BOILER MAC-205 Exhaust Port Intake Port Utica Boiler ITEM MAC-205 Pump Flow Sensor Flow Sensor with Water Filter and Flow Restrictor DHW Priority Sensor DHW Heat Exchanger Gas Valve NTC DHW Sensor Low Water Pressure Cutoff 3-Way Valve with Motor NTC Heating sensor (Flow/Return) QTY 2, (1 Shown for clarity)
4 - LOCATING BOILER WARNING TABLE 1: BOILER CLEARANCES Fire Hazard! Do not install on carpeting. Failure to Manufacturer Combustible follow these instructions could result in death or Dimension Recommended Materials serious injury. for Service (1)(2) 0" (0 cm) 8-5/8" (220 mm) 4.1 Boiler Location Considerations Left Side 1-3/4"...
4 - LOCATING BOILER 4.2 Clearances Service Clearances 100, 115, 125 & 150 165 & 205 13 9/16 in 211/2 in [345 mm] [571.5 mm] Front View of Left Side View Boiler of Boiler 8 5/8 in [220 mm] 17 3/4 in 1 3/4 3/4 in in 1 3/4 3/4 in in 13.58 in /...
4 - LOCATING BOILER FIGURE 4-2 Wall Mount Bracket (Included) CAUTION Boiler weight exceeds 140 pounds (63.5 kg). Do not lift boiler onto wall without assistance. Center brackets. Avoid overhang on sides of wall mount bracket. Lift boiler using chassis. Do not use front jacket, Note vent piping, water or gas fittings to lift boiler as it may cause damage to the boiler.
5 - COMBUSTION AIR AND VENT PIPING • Venting shall be supported adjacent to each joint using WARNING steel strapping or equivalent. See Figure 5-1. Fire, explosion, and asphyxiation hazard. Improper • Support horizontal sections of vent pipe to prevent sags installation could result in death or serious capable of accumulating condensate.
5 - COMBUSTION AIR AND VENT PIPING 5.2 Removal of Existing Boiler From Common Vent 5.3 Definitions System Coaxial piping – Exhaust and air intake pipe have a When existing boiler is removed from common venting common axis. system, common venting system is likely to be too large for proper venting of appliances remaining connected to it.
5 - COMBUSTION AIR AND VENT PIPING Venting shall be properly supported. WARNING Boiler shall not support any type of vent system. Manufacturer recommends this condensing boiler be All piping, glue, solvents, cleaners, fittings and vented with approved polypropylene venting material. components must conform to ASTM and ANSI standards.
Page 24
5 - COMBUSTION AIR AND VENT PIPING VENT MATERIAL OPTIONS (Maximum Equivalent Vent Length Shown) 100/115/125/150 Intake Exhaust Combined Vent Vent Vent (L1) (L2) (L1+L2) Vent Size Type Material 85 ft 6 ft 85 ft 6 ft 170 ft 12 ft 2"...
5 - COMBUSTION AIR AND VENT PIPING 5.6 Coaxial Venting Instructions WARNING Maximum equivalent flue lengths for Coaxial venting are: Asphyxiation hazard. Before securing the screws Coaxial Pipe Vent Lengths ensure the pipe has been pushed in a minimum of (Includes First Elbow And Termination) 1-3/4"...
5 - COMBUSTION AIR AND VENT PIPING 5.7 Coaxial Vent Screw Placement - See Figure 5-2 Two (2) screws shall be fastened through the outer intake pipe behind the gaskets at equal distances, approximately 180° apart. Note the screws used must be no larger than No. 8-3/4 sheet metal screws and must be zinc coated.
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-8 - 2"/60 mm & 3"/80 mm Twin Pipe WARNING Separated Horizontal Flue Termination Asphyxiation hazard! Improper installation could result in death or serious injury. Read Twin Pipe This Termination Installation Instructions completely and understand all can be used on: requirements before beginning installation.
5 - COMBUSTION AIR AND VENT PIPING Figure 5-11 - Natalini Clamp WARNING Asphyxiation hazard! Improper installation could result in death or serious injury. Read Twin Pipe Installation Instructions completely and understand all requirements before beginning installation. 5.9 Securing Twin Pipe Polypropylene Venting Venting manufacturer's use a device to secure Note single wall twin pipe polypropylene vent pieces...
Page 29
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-14 - (2"/ 60 mm & 3" / 80 mm) Twin Pipe 12" (305 mm) Min. horizontal separation Roof Vent CAN BE USED ON ALL SIZES between combustion air intake and vent of same appliance.
Page 30
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-17 -Twin Pipe Side Wall Vent (Multiple FIGURE 5-20 - (2"/ 60 mm ONLY) Vent Pipe with T Appliances) CAN BE USED ON ALL SIZES NOTE: 3" shown for clarity. 12" between vent and combustion air of other boilers This Termination required in all multiple boiler installations.
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-24 - (3" / 80 mm Only) Flexible Venting 5.10 (3" / 80 mm Only) Flexible Vent System System CAN BE USED ON ALL SIZES Flexible Pipe Minimum & Maximum Vent Lengths 100/115/125/150 165/205 3”...
Page 32
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-25 - Flue Terminal Location All vent pipe and combustion air pipe and fittings shall comply with the following: Use only manufacturer approved venting materials or venting materials primer and glue approved to: ULC S636 in Canada, or UL 1738 in the U.S.
5 - COMBUSTION AIR AND VENT PIPING FIGURE 5-26 - Condensate Drain WARNING Asphyxiation hazard! Fill condensate trap before starting boiler to avoid combustion products escaping boiler. Failure to follow these instructions could result in death or serious injury. Do not glue cap 5.11 Condensate Piping on if used for •...
6 - HYDRONIC PIPING FIGURE 6-2 Safety Relief Valve Discharge Piping WARNING Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions. Safety Relief Valve 6.3 Safety Relief Valve and Air Vent •...
6 - HYDRONIC PIPING 6.4 Trim Piping • Temperature - Pressure Gauge. Install temperature pressure gauge using piping provided with boiler. See Figure 6-1. • Some boiler models may have integral drain valve located inside jacket directly underneath pump. Install provided external drain valve as required.
Page 37
6 - HYDRONIC PIPING FIGURE 6-3 - Piping Diagram - LWCO Location Arrange piping to prevent Low Water Cutoff (LWCO) Note (See Figure 6-5 for detail) water dripping onto boiler. Illustrations are meant to Note show system piping concept Purge Valve only.
6 - HYDRONIC PIPING 6.6 External Optional Low Water Cut Off FIGURE 6-5 - Low Water Cutoff - Detail These guidelines are supplied when necessary to install an additional Low Water Cut Off (LWCO), for sensing a low water level condition in a boiler, as required by the Authority Having Jurisdiction.
6 - HYDRONIC PIPING 6.7 Manufacturer Recommendation - Strainer on DHW Inlet Potable water Potable water Manufacturer Recommendation Manufacturer strongly recommends the use of a strainer filtering potable water before entering the boiler. The strainer prevents any sedimentation and debris from your water supply piping from entering the boiler.
6 - HYDRONIC PIPING 6.8 Central Heating System • Flow of water, certain minimums are required, will operate the DHW flow switch which requests the 3 way valve to Boiler is designed for use in a sealed central heating system. change position.
• Do not touch any electrical switch; do not use any GAS SUPPLY REQUIRED: phone in your building. NATURAL GAS LIQUID PROPANE MODEL • Immediately call your gas supplier from a neighbor’s phone. Follow gas supplier’s MAH-100 92 ft3/h 2.60 38 ft3/h 2.61 m3/h) m3/h) instructions.
7 - GAS SUPPLY PIPING 7.2 Gas Pipe Recommendations • Use of Gas Appliance Connectors (flexible connectors Configure gas pipe for proper operation and avoid issues typically used for gas stoves or water heaters) is with failure to light or maintenance of proper flame during prohibited.
Page 43
7 - GAS SUPPLY PIPING This chart is sourced from NFPA-54 2015 with the BTU ratings for the material, length, and diameter of gas pipe. INTENDED USE: Pipe Sizing Between Natural Gas Meter, or Propane Single - or Second-Stage (Low-Pressure) Regulator and Appliance.
7 - GAS SUPPLY PIPING NOTICE FIGURE 7-1 Sediment trap shall be located upstream of gas controls. 7.3 Leak Check Gas Piping Pressure test boiler and gas connection before placing boiler in operation. • Pressure test over 1/2 psig (3.5 kPa). Disconnect boiler and its individual gas shutoff valve from gas supply system.
8 - ELECTRICAL CONNECTIONS DANGER Model Size Electrocution Hazard! HIGH VOLTAGE - Connections Power Supply 120V - 60Hz in terminal block M1 are high voltage (120V / 60Hz). Before making connections, verify appliance is Power 118 W 125 W 133 W 142 W 173 W 182 W disconnected from power supply.
8 - ELECTRICAL CONNECTIONS FIGURE 8-2 Terminal Block Locations DANGER Electrocution Hazard! HIGH VOLTAGE - Connections in terminal block M1 are high voltage (120V / 60Hz). Before making connections, verify appliance is disconnected from power supply. Respect the input polarity on terminal block M1: L (LINE) - N (NEUTRAL). Failure to follow these instructions WILL result in death or serious injury.
8 - ELECTRICAL CONNECTIONS FIGURE 8-4 End Switch Connections 8.6 Install Room End Switch Install room end switch on inside wall. Do not install where it will be influenced by drafts, hot or cold water pipes, lighting fixtures, television, sun rays or near a fireplace. Dry contact only - do not apply 24 volts between 6 and 7.
Page 48
8 - ELECTRICAL CONNECTIONS FIGURE 8-6 Kt Climate Curves Flow temp Outside temp 80 Is Default. NOTE: Temperatures below -40 °F (-40 °C), maximum heating flow temperature set point no longer increases, curves shown on graph become horizontal. Boiler set-point will override sensor set-point. 240013354 REV B [09/15/2021]...
8 - ELECTRICAL CONNECTIONS FIGURE 8-7 Kt Indirect Storage Tank 8.8 Indirect Storage Tank Boilers MAH-100, MAH-125 can be electrically connected to *125 Model shown - See Application Guide for size 100 indirect storage tank as follows: 10K Ω sensor NTC to terminals 3-4 •...
Page 50
8 - ELECTRICAL CONNECTIONS FIGURE 8-8 Circulator Pump Connections For more information please review the application guide received with your boiler. 240013354 REV B [09/15/2021]...
9 - START UP PROCEDURE 9.1 Central Heating System Connections - HEAT ONLY MAH-100 & MAH-125 HEAT ONLY MAH-165 HEAT ONLY WITH OPTIONAL INDIRECT DHW CONNECTION MAH-100 & MAH-125 HEAT ONLY WITHOUT OPTIONAL INDIRECT DHW CONNECTION LEGEND 100 / 125...
9 - START UP PROCEDURE 9.3 System Start Up FIGURE 9-1 Condensate Drain Assembly Follow all codes and regulations when filling the boiler. Model 205 shown (location similar in all sizes) Use drain taps to allow system to completely drain. Thoroughly flush the heating system before boiler is connected and again after first heating season.
9 - START UP PROCEDURE 9.5 Control Panel To enter the INFO Menu press and hold for 1 second. Press and hold the button for 1-2 seconds to increment through the selections as shown in the table below. Press to exit. DESCRIPTION DESCRIPTION Secondary fault internal code...
9 - START UP PROCEDURE WARNING Boiler must not shutoff during calibration. Note Open all heating zones in heating or DHW Asphyxiation hazard! Fill condensate trap before mode to ensure boiler does not shutoff. starting boiler to avoid combustion products escaping 9.8 Automatic Calibration Function boiler.
9 - START UP PROCEDURE 9.10 De-Aeration Function NOTICE Used to eliminate air inside the heating circuit when boiler is installed or after maintenance when water is drained from During initial ignition, burner may not ignite. This may primary circuit. cause boiler to shut down until any air in gas pipes is Press buttons together and hold for 6 seconds.
9.12 Chimney Sweep Function For correct boiler operation, content of (CO ) in the combustion flue must be within tolerances indicated in table below. Gas A (Natural Gas) Gas E (LPG) Combustion MAH-100 MAH-165 MAH-125 Table MAC-115 & 150 MAC-205...
9 - START UP PROCEDURE Table 9-2 Input Rate @ High Fire (MBH) For Natural Gas : 3600 x cu ft Approximate Rate @ Input (MBH) 100% Fire (MBH) seconds Size Example: Natural Gas - Gas flow from 93.5 Meter = 2 cu ft Measured time = 72 seconds 3600 x 2 cu ft = 100 MBH...
Page 59
9 - START UP PROCEDURE FACTORY SETTINGS 9.16 Description Of Parameters: Factory Settings conti. 115, 100, 150,205 125,165 P11..P12 Manufacturer information Max. heating output (0-100%) DHW max. output (0-100%) Min. heating output (0-100%) Maximum CH set-point (°C) 00 = 176°F (80°C) 01 = 113°F (45°C) Selectable Range 20-80 = (20°C to 80°C) 68°F to 176°F Pump overrun time in heating mode (01-240 minutes)
Table showing parameter P13 values according to desired maximum power model is shown for each single boiler. To access and edit P13 values, proceed as described in Section 9.15 Parameter Settings. Boiler Model - PARAMETER P13 (%)/ Heating Output Btu/h MAH-100 MAC-115 17,060 20,473 23,885 27,297 30,709 34,121 10.0...
10 - OPERATING INSTRUCTIONS 10.2 Boiler Operation FOR YOUR SAFETY READ BEFORE OPERATING Domestic hot water supply always takes priority over central WARNING heating. If you do not follow these instructions exactly, Demand for hot water required during central heating period, a fire or explosion may result causing property boiler automatically switches to hot water mode until demand damage, personal injury or loss of life.
10 - OPERATING INSTRUCTIONS 10.5 Frost Protection Boiler monitors supply and return water temperatures to enable frost protection which automatically turns boiler and pump on. If water in boiler falls below 41°F (5°C), providing boiler is connected to power, boiler will operate until water temperature in the system reaches approximately 86°F (30°C).
11 - GENERAL MAINTENANCE AND CLEANING • Circulator pump and combustion air blower motor furnished DANGER with boiler are permanently lubricated from factory and require no further lubrication. Lubricate field sourced Before servicing, turn off electrical power to boiler at pumps and/or motors according to pump and/or motor service switch.
11 - GENERAL MAINTENANCE AND CLEANING WARNING 11.2 Maintenance And Routine Servicing Check and service boiler as necessary. Following service procedures must be performed by Frequency of servicing will depend upon installation qualified service agent. Boiler owner shall not attempt conditions and usage, manufacturer recommends annually.
11 - GENERAL MAINTENANCE AND CLEANING DANGER Before servicing, turn off electrical power to boiler at service switch. Close manual gas valve to turn gas supply OFF to boiler. Failure to comply will result in death or serious injury. 11.4 Draining the Boiler •...
11 - GENERAL MAINTENANCE AND CLEANING 11.6 Hydraulic Unit (DHW) Model MAC-150 SHOWN For special areas, where water is harder than 200 ppm or 12 grains/ gallon, install polyphosphate dispenser or equivalent treatment system, compliant with current regulations. 11.7 Cleaning The Cold Water Filter Boiler is fitted with cold water filter located on DHW hydraulic assembly (B).
11 - GENERAL MAINTENANCE AND CLEANING 11.10 User Information NOTICE Advise and demonstrated to User the following important information: When servicing the appliance, check the condition and A. How to light and turn off boiler. How to operate position of flame sensing electrode and replace it if system controls.
Input, MBH (KW) Domestic Hot Water (DHW) Circuit Heating Model Altitude AFUE, % Capacity, Max Input, Min Input, Max Output, Min Output, Number Maximum Minimum MBH* MAH-100 88.8 16.5 81.1 95.0 MAC-115 88.8 16.5 81.1 95.0 109.7 16.6 100.2 15.3 MAH-125 95.0...
Page 70
12 - RATINGS AND CAPACITIES 12.5 Available Pump Head For Central Heating This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The automatic air valve incorporated in the pump allows quick venting of the heating system. WATER FLOW RATE Minimum speed of modulation HEAD...
13 - TROUBLE SHOOTING 13.2 Anomalies Table for the Installer - Use this table to report the anomaly values. SYSTEM STATUS CODES 0 STANDBY 1 DHW "ON" 2 CHIMNEY SWEEP ACTIVE 3 CH "ON" 4 PREHEAT "ON" 5 CH NO FROST "ON" 6 DHW NO FROST "ON"...
14 - GLOSSARY • APPLIANCE - Device to convert gas into energy; term • DIRECT VENT BOILER - Boiler constructed and installed so includes any component, control, wiring, piping or tubing all combustion air is derived directly from outdoors and all required to be part of the device.
Page 75
14 - GLOSSARY • METRIC GAS METERS • TWO PIPE SYSTEM - Type of venting that allows for exhaust flue and intake air piping to be separated from each Natural Gas other. Fresh air may be drawn in at a different area from 127,116 x cu meters where flue terminal is located.
Page 83
INSTALLATION AND CHECK-OUT CERTIFICATE Boiler Model Serial # Date Installed___________ Measured BTU/HR input____________ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner/ maintenance person Installation booklet affixed on or adjacent to boiler Installer (Company) Address Phone...
Page 84
IMPORTANT In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function.
Page 85
APPLICATION GUIDE FOR USE WITH HEATING ONLY - 100, 125, 165 & COMBI - 115, 150, 205 This manual has been prepared for use with the appropriate Installation, Operation and Maintenance Manual. Manufactured by: ECR International Inc. 2201 Dwyer Avenue, Utica, NY 13501 Tel.
Page 86
TABLE OF CONTENTS Important Safety Information .....................3 Labor Saving Piping Manifolds / Near Boiler Piping Connections ..........4 General Information - Hydronic Piping ..................6 General Information - Wiring ......................8 Piping and Wiring Diagrams Piping Legend ..........................9 100, 125 W/Zone Circulators & DHW Tank - Piping Diagram ............10 100, 125 W/Indirect Zone Circulators, DHW Tank W/Sensor - Wiring Diagram .......
IMPORTANT SAFETY INFORMATION 3. Installation shall conform to requirements of 1. 1. Become familiar with symbols identifying Become familiar with symbols identifying authority having jurisdiction or in absence of such potential hazards. potential hazards. requirements: • United States • National Fuel Gas Code, ANSI Z223.1/NFPA 54. This is the safety alert symbol.
GENERAL INFORMATION - HYDRONIC PIPING FOR YOUR SAFETY READ BEFORE OPERATING WARNING Burn and scald hazard! Manufacturer requires installation of field supplied anti-scald valve. DANGER Failure to follow these instructions could result in death or serious injury. General Information: Piping installation, materials, and joining methods shall conform to requirements of authority having jurisdiction or in absence of such requirements: •...
Page 91
GENERAL INFORMATION - HYDRONIC PIPING Water 1st Degree Burn 2nd and 3rd Degree Burn Use of Indirect Water Heater (DHW) Heating Temperature Exposure Time For Exposure Time For An Setting An Adult Adult Only Boiler: 120° F 1 minute 5 minutes 130°...
GENERAL INFORMATION - WIRING Electrical Wiring Information: DO NOT use 120 V thermostat Note terminals (M1- #1 and #2). All field wiring shall conform to the authority having jurisdiction or, in the absence of such requirements to: • USA: National Electrical Code, ANSI/NFPA 70, Provided Wiring and Piping •...
EXTERNAL BUFFER TANK - PIPING DIAGRAM Buffer Tank Piping When installing low mass systems, additional water mass may be required to avoid short cycling by the boiler. In these applications it is recommended that a buffer tank be installed. Buffer Tank on Central Heat Circuit Using Internal Boiler Circulator Note: •...
Page 109
EXTERNAL BUFFER TANK - PIPING DIAGRAM Buffer Tank On Central Heat Circuit With Primary Pump and Supplied Manifold NOTE : Acceptable primary pump locations: Either 1 or 2. For pump wiring see diagrams on pages 26-29. PN 240011430 REV. P [09/15/2021]...
EXTERNAL BUFFER TANK - WIRING DIAGRAM Buffer Tank Pump Wiring Controlling A Primary Pump On A Combi Boiler With Zone Valves, No Indirect Tank PN 240011430 REV. P [09/15/2021]...
Page 111
EXTERNAL BUFFER TANK - WIRING DIAGRAM Buffer Tank Pump Wiring Controlling A Primary Pump On A Combi Boiler With Zone Pumps, Argo ARM 4P Zone Control and A822-II PN 240011430 REV. P [09/15/2021]...
Page 112
EXTERNAL BUFFER TANK - WIRING DIAGRAM Buffer Tank Pump Wiring Controlling A Primary Pump On A Combi Boiler With Zone Valves and Indirect Tank With Priority Argo UZ3 and AR22II Zone Controls ZONE VALVES ZONE VANNES DE ZONE THERMOSTATS 4 Wire Valve Domestic Hot Water Tank Buffer Tank...
OPTIONAL EQUIPMENT Optional Equipment IMPORTANT: Sensors supplied with this boiler are proprietary to the manufacturer. Use of alternate market sensors WILL diminish boiler performanc Outdoor Air Sensor, if used. 1k Ω A. Boiler automatically recognizes sensor when used. B. See Chart 1 for sensor data. Sensor part number BD710487302V C.
ACCESSORIES 1. 1K Ohm (1K Ω) Outdoor Temperature 1k Ω Sensor Kit - BD710487302V • Use the Outdoor Sensor (OAS) Kit with Heating Only or Combi Boilers. • Wire Control to boiler M2 terminal strip, terminals 4 and 5 as shown. •...
Page 115
ACCESSORIES 2. 10k Ω Indirect Storage Tank Sensor Kit Parameter PO3 for Heating Only boiler, with no Note indirect tank remains Factory Set at 08. No change Heating Only boiler can be electrically connected to is required. Indirect Storage Tank. Diagram of electrical connection of external indirect If adding an Indirect Tank with a sensor to storage tank is shown below.
APPLICATION TABLE - INDIRECT HOT WATER TANK PERFORMANCE CHART HEATING ONLY BOILERS 100, 125, 165 BOILER OUTPUT NEEDED FOR MAXIMUM PERFORMANCE Notes: 176 °F Boiler Supply Water Temperature, AHRI Conditions -50 °F Inlet Water @ 240 GPH Flow Rate. PN 240011430 REV. P [09/15/2021]...
LOW WATER CUTOFF • Locate LWCO sensing device in the supply Low Water Cut Off - Heating Only and Combi Boilers piping, above the minimum height of boiler. See Figure page 42, Piping Diagram. These guidelines are supplied when necessary to install an additional Low Water Cut Off (LWCO), for sensing a •...
LOW WATER CUTOFF Piping Diagram - LWCO Location Arrange piping to prevent water dripping onto boiler. Note Illustrations are meant to show system piping concept only. Installer Note is responsible for all equipment and detailing required by authority having jurisdiction. Air Vent Position LWCO Above Top of Boiler...
ERROR CODE TABLE Initial Fault Finding Checks Note: When instructed press and hold “RESET” for between 1-3 seconds to reset the boiler. Check gas, water and electrical supplies are available at the boiler Table of Error Codes Electrical supply = 120V ~60 HZ Gas Valve Connection Cable The preferred minimum gas pressure is 3.5”...
FAULT SOLUTION SECTIONS Fault Finding Solutions Sections Power supply 120V Main terminals L and N Check electrical supply Connection OK at connector x1 0 Integrity of the fuse Replace fuse Main or Display Display PCB fault illuminated PCB - X1 0 connector Check wiring Mains terminals L &...
Page 132
FAULT SOLUTION SECTIONS PN 240011430 REV. P [09/15/2021]...
Page 133
FAULT SOLUTION SECTIONS Overheat thermostat operated or Check for and correct any system faulty. faults (water circulation). Allow to cool. Continuity �I across thermostat terminals � Replace safety thermostat '---------------' more than 1.5 ohm Is E11 O is still flashing Check Flow, Return, Replace PCB sensors.
Page 134
FAULT SOLUTION SECTIONS PCB connector x22 Hall With water running effect sensor terminals. Is main water filter and through DHW circuit, Check the voltage is Check DHW NTC assembly clean and measure red and white Replace PCB approximately 5 VDC senor for proper OHM rotor free to move? wire for 2.8 VDC for...
Page 137
IMPORTANT INFORMATION READ THIS LEAFLET BEFORE COMMISSIONING THE BOILER IMPORTANT: Upon startup of this new boiler please call ECR International, Inc. Technical Support for installation assistance and registration. Technical Support and Product Registration Monday - Friday 8AM to 6PM Eastern time. 1.800.253.7900 Described below is the procedure to activate the Commissioning Function wihich includes De-Aeration Function/Gas Type Check when power is first supplied to the boiler and the actions required when on a Gas E (LPG) supply.
Page 138
INFORMATIONS IMPORTANTES LIRE CET IMPRIMÉ AVANT DE METTRE LA CHAUDIÈRE EN MARCHE IMPORTANT : Lors du démarrage de cette nouvelle chaudière veuillez appeler recueil International, Inc. de support technique pour l'assistance à l'installation et l'enregistrement. Support technique et enregistrement du produit lundi - vendredi 8h00 à...
Page 139
Required Inspection Schedule To Be Completed By Qualified Service Technician Date Completed Inspection Items Year Year Year Year Check boiler and system piping for any sign of Near boiler piping leakage, verify pipes are properly supported. Check condition of all vent pipes and joints. Verify Vent vent piping terminations are free of obstructions Piping...