Venting System Inspection & Installation - UTICA BOILERS SFH 5 Series Installation, Operation & Maintenance Manual

Water oil fired cast iron boiler
Table of Contents

Advertisement

Chimney construction shall conform to the requirements
of authority having jurisdiction or in absence of such
requirements NFPA 211, Standared for Chimneys,
Fireplaces, Vents and Solid-Fuel Burning Appliances.
Venting system installation shall conform to the
requirements of the authority having jurisdiction or in the
absence of such requirements, to NFPA 31 - Standard for
the Installation of Oil Burning Equipment.
1.
INSPECT CHIMNEY
• Boiler shall be installed into chimney which has
masonry or metallic chimney liner�
• An unlined chimney will have leaks that will cause
poor chimney performance (NO DRAFT), and could
result in positive pressure in combustion chamber�
• Horizontal portions of venting system should
not exceed 10 feet in length� Horizontal lengths
over 10 feet will have negative effect on chimney
performance�
• Chimney should extend at least 2 feet above any
portion of building within 10 feet� See Figure #16�
It should produce negative draft of �06 to �08 inches
of water column, (W�C�), as measured with draft
gauge between boiler and barometric draft control
while maintaining �02 inch W�C� negative draft in
combustion chamber�
• Inadequate draft will cause improper combustion,
resulting in dirty flue ways and high fuel bills.
2.
CONNECT FLUE PIPE
• Connect flue pipe same size as boiler outlet to
chimney, sloping upward continuously toward
chimney approximately ¼" per foot� Bolt or screw
joints together to avoid sag�
• If oil fired water heater is vented into same flue as
boiler, provide separate hole into chimney whenever
possible� When not possible, use "Y" connection in
flue pipe, using separate draft regulator for each unit.
• When chimney will not provide adequate draft
to handle input from water heater and boiler
simultaneously, wire units so that only one will
operate at a time, favoring water heater�
9 - VENTING SYSTEM INSPECTION & INSTALLATION
Figure #16
18
PN 240013073, Rev. A [08/31/2020]