Start-Up; How To Start The Device; Start-Up Checklist; Operating Concept - KROHNE OPTIWAVE 1010 Quick Start Manual

Radar (fmcw) level transmitter for bypass chamber and magnetic level indicator
Hide thumbs Also See for OPTIWAVE 1010:
Table of Contents

Advertisement

OPTIWAVE 1010

4.1 How to start the device

4.1.1 Start-up checklist

Do a check of the device's condition before you energize the device:
• Are all the wetted components (PEEK element, matching element and gaskets) resistant to
the product in the tank?
• Does the information on the device nameplate agree with the operating data?
• If the device is supplied with a magnetic (bypass) level indicator:
If the device is supplied with a magnetic (bypass) level indicator:
If the device is supplied with a magnetic (bypass) level indicator: Did you correctly install the
If the device is supplied with a magnetic (bypass) level indicator:
magnetic level indicator adjacent to the tank?
• If the device is supplied with a magnetic (bypass) level indicator:
If the device is supplied with a magnetic (bypass) level indicator: Did you remove the float lock
If the device is supplied with a magnetic (bypass) level indicator:
If the device is supplied with a magnetic (bypass) level indicator:
pin from the side process connection at the bottom of the bypass chamber?
• Do the electrical connections agree with the national electrical codes? Use the applicable
electrical cables with the cable glands.
DANGER!
Before you energize the device, make sure that the supply voltage is correct.
DANGER!
Safe operation in hazardous locations
Safe operation in hazardous locations
Safe operation in hazardous locations
Safe operation in hazardous locations
Make sure that the installation and the wiring of the device agree with the related Ex standards
and regulations. Make sure that the device has the applicable Ex approval for the hazardous
location. For more data, refer to the related Ex certificate of conformity and the supplementary
instructions.
4.1.2 How to start the device
• Connect the converter to the power supply.
• Energize the converter.
INFORMATION!
The manufacturer sets the parameters for your application in the factory. The 0% level (empty) is
aligned with the center of the bottom process connection and the 100% level (full) is aligned with
the center of the top process connection. You can use the HART communication protocol to
change these parameters.

4.2 Operating concept

You can read measurements and configure the device with:
• A connection to a system or PC with PACTware™. You can download the Device Type
Manager (DTM) file from the website. It is also supplied on the DVD-ROM delivered with the
device.
• A connection to a system or PC with AMS™. You can download the Device Description (DD)
file from the website. It is also supplied on the DVD-ROM delivered with the device.
• A connection to a HART® Field Communicator. You can download the Device Description (DD)
file from the website. It is also supplied on the DVD-ROM delivered with the device.
For more data about how to use the DTM in PACTware, refer to the "Operation" chapter in the
handbook. For more data about the menu tree for the Basic-DD, AMS and PDM, refer to the
"Description of HART interface" chapter in the handbook.