Download Print this page
Hytronik HCD418 Manual

Hytronik HCD418 Manual

Dali hf sensor

Advertisement

Quick Links

DALI HF Sensor
HCD418
Tri-level Control for Independent DALI
Applications
Occupancy detector with tri-level control suitable for indoor use.
Suitable for building into the xture:
Of ce / Commercial Lighting
Classroom
Meeting Room
Use for retro t and new luminaire designs/installations
Features
Tri-level dimming control based upon occupancy (also known as corridor function)
TM
DALI dimming control method (DALI power supply circuit included)
5-Year Warranty
Technical Data
Input Characteristics
Model No.
Mains voltage
Stand-by power
Switched power
Warming-up
Safety and EMC
EMC standard (EMC)
Safety standard (LVD)
Radio Equipment (RED)
Certi cation
RED
Subject to change without notice.
HCD418
120~277VAC 50/60Hz
<0.5W
Max. 15 devices, 30mA
20s
EN55015, EN61000
EN60669, AS/NZS60669
EN300440, EN301489,
EN62479
Semko, CB, CE , EMC, RED, RCM
IP20
Sensor Data
Model No.
Sensor principle
Operation frequency
Transmission power
Detection range
Detection angle
Setting adjustments:
Sensitivity
Hold time
Daylight threshold
Stand-by period
Stand-by dimming level
Environment
Operation temperature
Case temperature (Max.)
IP rating
Edition: 26 Feb. 2020
HCD418
High Frequency (microwave)
5.8GHz +/- 75MHz
<0.2mW
Max. ( O x H) 12m x 6m
30
O
~ 150
O
10% / 50% / 75% / 100%
30s ~ 30min (selectable)
2 ~ 50 lux, disabled
0s ~ 1h, +∞ (selectable)
5% / 10% / 20% / 50%
Ta: -35
O
C ~ +70
O
C
Tc: +80
O
C
IP20
Ver. A0
Page 1/5

Advertisement

loading
Need help?

Need help?

Do you have a question about the HCD418 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hytronik HCD418

  • Page 1 DALI HF Sensor HCD418 Tri-level Control for Independent DALI Applications Occupancy detector with tri-level control suitable for indoor use. Suitable for building into the xture: Of ce / Commercial Lighting Classroom Meeting Room Use for retro t and new luminaire designs/installations...
  • Page 2: Functions And Features

    Tri-level Control (Corridor Function) Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light -->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period;...
  • Page 3: Detection Pattern

    Semi-auto Mode (Absence Detection) It is easy to forget to switch off the light, in of ce, corridor, even at home. And in many other cases, people do not want to have a sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no need to have the light on. The solution is to apply this “absence detector”: motion sensor is employed, but only activated on the maunal press of the push switch, the light keeps being ON in the presence, and dims down in the absence, and eventually switches off in the long absence.
  • Page 4: Dip Switch Settings

    Wiring Diagram N Push DA+ DA DA DA DA DA HCD418 Max.15pcs DALI Driver DALI Driver DIP Switch Settings Detection Range I – 100% 100% II – 75% Sensor sensitivity can be adjusted by selecting the combination on the DIP III –...
  • Page 5 Additional Information / Documents 1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation 2. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy Subject to change without notice.