(2) For A97*/960GOT
• Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
• Pass the grounding braided wire on the programmable logic
controller side through the core.
GOT side
130
(5.12)
Within 150
(5.90)
3) Computer link connection
a) For RS-232C cable
The RS-232C cable used to connect the GOT, the computer link
module PLC CPU with computer link function must be prepared by the
user.
The RS-232C cable connection diagram and the connector are as
follows.
(1) Connection diagram
• If D-sub 9-pin is used for the connector of the computer link module.
(A1SJ71QC24(-R2), A1SJ71UC24-R2, A1SJ71C24-R2,
A1SCPUC24-R2, A2CCPUC24, QJ71C24(-R2))
GOT side
Signal
Pin No.
CS(CTS)
8
RS(RTS)
7
CD
1
RD(RXD)
2
SD(TXD)
3
DTR(ER)
4
DSR(DR)
6
SG
5
-
9
Shell
Ferrite Core
(ZCAT3035-1330)
Cable shield material
Grounding braided
wire(50mm(1.97inch))
Braided shield
31
PLC side
130
(5.12)
Within 150
Unit : mm (inch)
(5.90)
Computer link module side
Pin No.
Signal
1
7
RS(RTS)
8
CS(CTS)
3
SD(TXD)
2
RD(RXD)
6
DSR(DR)
4
DTR(ER)
5
9
CD
SG
-
Shell

Advertisement