Emc Directive - Mitsubishi GOT MELSEC A985GOT-TBA-EU User Manual

Table of Contents

Advertisement

1.1.1 EMC Directive

The standards of the EMC Directive are shown below.
Specification
EN55011
Radiated noise
EN61000-6-
4 :2001
EN55011
Conducted noise
EN61000-4-2
Electrostatic
immunity
EN61000-4-4
Fast transient burst
noise
EN61131-2 :
*
1994/A12
(2000)
EN61000-4-3
Radiated field AM
modulation
EN61000-4-12
Damped oscillatory
wave immunity
*1 QP: Quasi-peak value, Mean : Average value
*2 The GOT is an open type device (device installed to another device) and
must be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is
installed on the conductive control panel and combined with the Mitsubishi
PLC.
Test item
Electromagnetic emissions
from the product are
2
*
measured.
Electromagnetic emissions
from the product to the
2
*
power line is measured.
Immunity test in which static
electricity is applied to the
2
cabinet of the equipment.
*
Immunity test in which burst
noise is applied to the
2
power line and signal lines.
Immunity test in which field
is irradiated to the product.
2
*
Immunity test in which a
damped oscillatory wave is
superimposed on the power
2
*
line.
Test details
2
Standard value
30 M-230 MHz QP:
30 dBµ V/m (30 m in
measurement range)
230 M-1000 MHz QP:
37 dBµ V/m (30 m in
measurement range)
150 k-500 kHz QP:79 dB,
Mean: 66 dB
1
*
500 k-30 MHz QP: 3 dB,
Mean: 60 dB
±15kV Aerial discharge
Power line: 2kV
Digital I/O (24V or higher):
1kV
(Digital I/O (24V or less)) >
250V
(Analog I/O, signal lines) >
250V
10V/m, 26-1000 MHz,
80%AM modulation@1 kHz
Power line: 1kV
Digital I/O (24V or higher): 1
kV
1
*

Advertisement

Table of Contents
loading

Table of Contents