5. HANDLING

5.1 Handling instructions

When mounting the main unit to a control panel or similar, set the display
section as shown below.
When the temperature inside the enclosure is 40 to 55°C or less, the
mounting angle should be in the range 60 to 105 degrees.
The GOT will be deteriorated earlier if it is used at the mounting angle other
than the above. Therefore, the temperature inside the enclosure should be
within 40°C.
Tighten the screws in the following specified range.
Terminal block terminal screw (M3 screw)
Module mounting screw (M4 screw)
Communication module mounting screw (M3 screw)
Communication board mounting screw (M3 screw)
Option module mounting screw (M3 screw)
SVGA type CRT mounting screw (M3 screw)
Case fixing screw (M3 screw)
Memory board mounting screw (M2.6 screw)
RS-232C connector mounting screw
(#4-40 UNC (inch screw))

5.2 Installation method

1) Mounting panel cutting dimensions
When mounting the GOT on a control panel door, user-made mounting
base or similar, the door or mounting base must be cut as indicated below.
A
Panel opening
GOT
Display
section
Enclosure, etc.
Screw Location
Type
A985GOT
A97*GOT
A960GOT
105°
60°
Tightening Torque Range
A [mm](inch)
302 (11.89)
[+1.0(0.04), −0(0)]
289 (11.39)
[+1.0(0.04), −0(0)]
258 (10.17)
[+1.0(0.04), −0(0)]
19
59 to 88N cm
36 to 48N cm
25 to 35N cm
20 to 28N cm
B [mm](inch)
228 (8.98)
[+1.0(0.04), −0(0)]
200 (7.88)
[+1.0(0.04), −0(0)]
183 (7.21)
[+1.0(0.04), −0(0)]