Daikin Sky Air FAA71BUV1B Service Manual page 78

Indoor units
Hide thumbs Also See for Sky Air FAA71BUV1B:
Table of Contents

Advertisement

4
|
Components
Service manual
78
Name
Symbol
Air thermistor
R1T
Heat
R2T
exchanger
thermistor
Intermediate
R3T
heat
exchanger
thermistor
4 Determine the thermistor resistance that matches the measured
temperature.
Thermistor – Table A
T °C
T °C
–20
197.81
10
–19
186.53
11
–18
175.97
12
–17
166.07
13
–16
156.80
14
–15
148.10
15
–14
139.94
16
–13
132.28
17
–12
125.09
18
–11
118.34
19
–10
111.99
20
Location (PCB) Connector
(pins)
A1P (I/U)
X16A:1‑2
A1P (I/U)
X18A:1‑2
A1P (I/U)
X17A:1‑3
T °C
39.96
40
10.63
38.08
41
10.21
36.30
42
9.81
34.62
43
9.42
33.02
44
9.06
31.50
45
8.71
30.06
46
8.37
28.70
47
8.05
27.41
48
7.75
26.18
49
7.46
25.01
50
7.18
Reference
(table)
A
A
A
T °C
70
3.44
71
3.32
72
3.21
73
3.11
74
3.01
75
2.91
76
2.82
77
2.72
78
2.64
79
2.55
80
2.47