VI. Pre-Installation and Mounting (continued)
D. AMP 400-1000L Stacking
1. The AMP 400-1000L models may be installed in a
stacked configuation.
a. One 400 or 500 model can be mounted on the top
of another 400 or 500 model.
b. One 650, 800, or 1000L model can be mounted
on the top of another 650, 800, or 1000L model.
2. Lifting the appliance for stacking.
a. Lifting with a forklift: Place forks center of the
base from the side.
 DANGER
Failure to center the lifting forks under the base of the
appliance could result in severe property damage or
injury.
b. Lifting with a crane: Remove top panel to access
the lifting lugs of the heat exchanger.
3. Stacking brace kit (PN: 111405-01) is included with
AMP 400-1000L models. The kit includes 2 braces
and 8 self drilling screws.
Figure 5: AMP 400-1000L Stacking Brackets and Dislplay Rotation
14
DANGER
a. Follow all previous instructions for mounting the
bottom appliance.
b. Use the included screws to secure the brace as
shown in Figure 5.
4. Outdoor AMP models cannot be stacked.
5. The display bracket on the top appliance can be
rotated for a better viewing angle of the Concert
display.
a. Remove the front panel and disconnect the wire
harnesses going to the display and the On/Off
switch.
b. Remove the 4 nuts holding the display bracket.
c. Unscrews the clamps holding the display onto the
display bracket to rotate the display 180°.
d. Reinstall the display, reinstall the display bracket
(Concert logo right side up), and connect the wire
harnesses.
Stacking Brace
Self-Drilling Screws
Rotated Display
(optionally field installed)
AMP 400-1000L I&O Manual