VIII. Condensate disposal (continued)
B. Condensate Neutralizer Installation
1. Some jurisdictions may require that the condensate
be neutralized before being disposed of. Follow local
codes pertaining to condensate disposal.
2. A condensate neutralizer kit is available from
factory as optional equipment. Refer to Table 17 for
size specific part number. Follow local codes and
instructions enclosed with the kit for condensate
neutralizer installation.
3. Limestone chips will get coated by neutral salts
(product of chemical reaction between limestone
and acidic condensate) and lose neutralizing
effectiveness over time. Therefore, periodic
condensate neutralizer maintenance and limestone
chip replacement are required for proper
neutralization of the condensate.
C. Common Condensate pump/Sump
1. A common condensate pump/sump may be used.
Run separate piping from each condensate drain
to the sump. A common drain may be used to
discharge condensate from the sump.
2. If a common sump is used, individual drain lines
should be constructed, using material listed above,
such that one drain cannot back feed into another
drain.
3. Do not manifold condensate and vent drains
together.
AMP 400-1000L I&O Manual
NOTICE
NOTICE
Flue gas condensate is corrosive. Route condensate
drain line in a manner such that any condensate
leakage will not cause property damage.
If the condensate line is obstructed in any way, the
float switch will prevent the appliance from firing.
Some jurisdictions may require that condensate
be neutralized prior to disposal.
The condensate drain trap should be flushed with
clean water as part of the appliance maintenance
schedule to remove any debris that might have
accumulated.
Table 17: Condensate Neutralizer Kit
Condensate
AMP
Neutralizer
Model
Kit, PN
400
107860-08
500
107860-08
650
107860-09
800
107860-09
1000L
107860-06
Condensate
Neutralizer,
Refill Kits, PN
107886-09
107886-09
107886-10
107886-10
107886-06