VI. Pre-Installation and Mounting (continued)
E. Clearances
1. The AMP is listedfor 0" clearance to combustible
materials. The clearances for serviceability are
found in Table 5.
2. Minimum clearances from combustible or
noncombustible construction, 0" sides, 0" back,
0" top.
3. It is the installers responsibility to provide enough
clearance for servicing the appliance in the installed
location.
F. Clearances (French)
1. Dégagements minimaux à assurer entre les parois
de l'appareil et les constructions combustibles ou
incombustibles : 0 po (côtés), 0 po (arrière) et 0
po (dessus).
2. Installation dans une garde-robe : assurer un
dégagement de 24 po devant l'appareil.
G. Closet and Alcove Installation
1. Include ventilation air openings in closet
installations.
2. Provide a 1" minimum clearance around water
pipes.
3. Follow vent material manufacturer for vent

clearances.

4. Clearances for closet or alcove Installation:
Front - 24"
Sides - 24"
Rear - 22"
Top - 20"
Table 5: AMP 400-1000L Clearances
Minimum
Front
Clearance
(In.)
Serviceability
(Indoor
24
Installation)
Serviceability
(Outdoor
24
Installation)
To
Combustible
0
Construction
* Leave 24" clearance on at least one side.
When installing under an overhang, conform to
**
local codes.
AMP 400-1000L I&O Manual
Rear
Right
Left
(In.)
(In.)
(In.)
24
0*
0*
36
0*
0*
0
0
0
This appliance is listed for zero inch clearance
to combustible or noncombustible material, but
installing the appliance with smaller than the
clearances for serviceability will limit access for
maintenance.
Consult local codes and inspectors before installing
multiple appliances adjacent to each other with
zero clearance.
Closet and alcove installation can cause elevated
temperatures. Follow the required clearances and
use only stainless steel, CPVC, or polypropylene
vent material.
Include ventilation air openings in closet
installations.
Do not install directly on carpeted flooring.
H. Side by Side and 0" Clearance Installation
1. When installing multiple appliances side by side,
never place one appliance inbetween two others
with zero clearance on both sides. Intall in couples
with at least 24 inches inbetween
Top
(In.)
0
0**
Figure 6: Side by Side installation
0
Do not install stacked pair of units 0" from another
stacked pair.
NOTICE
NOTICE
 WARNING
WARNING
24 in
 CAUTION
CAUTION
15