Appliance Mounting; Outdoor Installation - Thermal Solutions AMP 400 Installation, Operation And Maintenance Manual

Hot water boiler indoor/outdoor
Table of Contents

Advertisement

VI. Pre-Installation and Mounting (continued)
Table 4: Corrosive Combustion Air Contaminants
Contaminants to Avoid:
Spray cans containing chlorofluorocarbons
(CFC's)
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Anti-static fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms.
Adhesives used to fasten building products and
other similar products
Excessive dust and dirt
Areas likely to have contaminants:
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
B. Appliance Mounting
1. The AMP is intended for installation in an area with
a floor drain, or in a suitable drain pan to prevent
any leaks or pressure relief valve discharge resulting
in property damage.
2. This appliance is not intended to support external
piping or venting. All external piping and venting
must be supported independently of the appliance.
3. This appliance must be installed on a level surface
to prevent condensate from backing up inside the
heat exchanger.
4. Provide adequate space for condensate piping,
condensate pump, or neutralizer kit.
AMP 400-1000L I&O Manual
5. An elevaded base/pad is required when the floor is
not level or in areas where water could accumulate
around the appliance. The base must be able to
support the weight of the appliance, water, and all
additional system components.
a. This appliance is listed for installation on
combustible flooring. Acceptable flooring
includes a level metal or wooden base capable
of holding the weight of the appliance, water,
and aditional components. The base shall extend
beyond the edges of the appliance by at least 3
inches (76.2 mm) in any direction. Never install
directly on carpeted flooring.
b. For closet or alcove installation, the base shall
cover the entire floor of the closet/alcove.
6. Secure the appliance to its location using the 5/8"
anchoring holes on the feet of the base
C. Outdoor Installation
1. The outdoor trim of the AMP appliance is intended
for installation only in warm climates.
2. Install on a level permanent platform that keeps
the appliance free from standing water.
3. Three sides around the appliance must be open.
The louvered side of the appliance must be clear
of obstructions.
4. When installing under an overhang, conform to
local codes.
 WARNING
WARNING
For installation and operation only in climates
where the ambient temperature will not be less
than 32 °F (0 °C). Do not install in climates where
condensate can freeze.
Appliance must be protected from standing water.
Install on a level platform.
Do not install this appliance under an overhang
less than 3 feet from its top. The area under the
overhang must be open on 3 sides.
Never install directly on carpeted flooring.
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amp 500Amp 650Amp 800Amp 1000l

Table of Contents