7 Troubleshooting

7.1 Light Stack Indicators and Corrective Actions

Light Stack Fault Indicator
Solid Red light on Light Stack
DANGER
Flashing or Solid Amber light on
Light Stack
WARNING
Flashing Red light on Light Stack
Green Light
A green light indicates power has been applied to the controller, and the system is in normal
operating mode.
This light turns off when there is a fault or when in bypass mode.
Amber Light
The amber light flashes when the slowdown limit switch is triggered, or the distance measured with
the laser indicates the trolley or bridge motion has crossed into a slowdown area. The amber light
changes to steady state if the stop area is entered.
The amber light is turned off when in normal operation outside of a No-Fly zone.
Red Light
The red light turns on when a fault occurs in the controller or laser, or when the protected zone is
breached. The red light stays solid red until a breach or other fault is cleared. In this state all
control is stopped until the fault has been cleared.
The red light also flashes if no zones are configured such as on initial startup. In this state the red
light will flash until at least one zone is enabled.
The red light is turned off when in normal operation outside a No-Fly zone, and when there is no
fault with the lasers or controller.
Fault Name / Description
Zone [number] Breached
appears in Alarm List.
The hoist has entered the
slowdown or stop region of a
zone.
The NFZ system has been
bypassed or no protection
zones are enabled.
Corrective Action
1.
Disable the No-Fly Zone using the key
switch on the front of the enclosure
2.
Manually move the crane out of the
zone
3.
Adjust zone dimensions, slow down
distance, or stop distance
4.
Enable the No-Fly Zone by turning key
switch to Normal on front of the
enclosure
1.
Review the zone dimensions and adjust
as needed for slow down and stop
distances.
1.
The key switch on the front of the
enclosure is set to bypass the No-Fly
Zone protection
2.
All zones have been disabled using the
user interface
Intelli-Protect User Manual
April 2023
Page 54 of 58