Config Screens
Trolley – Setup Trolley Span, and Slow and Stop Distance
Bridge – Setup Bridge Span, and Slow and Stop Distance
Zone – Setup and enable / disable up to 31 No-Fly zones

4.2 Configurable Initial Setup

For initial setup and zone configuration the following steps should be implemented:
1. Power up the system
2. Status light Green for Power on, red flashing for no zones configured (NO FAULT) (No Horn)
3. Configure the bridge and trolley distances
4. Configure Zone 1
a. Teach corner 1 by moving the crane or entering the data manually
b. Teach corner 2 by moving the crane or entering the data manually
c. Enable Hoist Upper Limit if needed
d. Enable Machine Down if needed (Only Available in zone one)
5. Move the crane out of the zone
6. Enable the Zone 1 (Check box indicates zone is enabled with a check mark)
7. Status light Green (Amber if crane is still in the stop or slow down zone)
8. Test Zone
9. Repeat steps for Zones 2-27
10. Configure (4) End-of-Travel Zones: Zones 28-31
If all zones are disabled using the user interface, the green light will stay on and a red light will flash (no
horn).