Outdoor Unit - Panasonic AQUAREA WH-ADC0912K6E5AN Service Manual

Hide thumbs Also See for AQUAREA WH-ADC0912K6E5AN:
Table of Contents

Advertisement

12.3 Outdoor Unit

Attached accessories
No.
Accessories part
Drain elbow
1
Rubber cap
2
Protective bushing
3
12.3.1 Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -28°C.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinery oil, etc.), it
lifespan maybe shorten.
When installing the product in a place where it will
be affected by typhoon or strong wind such as
wind blowing between buildings, including the
rooftop of a building and a place where there is no
building in surroundings, fix the product with an
overturn prevention wire, etc. (Overturn prevention
fitting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Model
WH-UXZ09KE5*,
ø12.7mm (1/2") Ø6.35mm (1/4")
WH-UXZ12KE5*
Example: For WH-UXZ09KE5*
If piping length is 30m, the quantity of additional refrigerant should be 1000g. [(30-10)m × 50 g/m = 1000g]
Qty.
1
8
2
Piping size
Gas
Liquid
Pump Indoor
Optional Accessory
No.
Base Pan Heater
4
CZ-NE3P
It is strongly recommended to install a Base Pan
Heater (optional) if the outdoor unit is install in
cold climate area. Refer the Base Pan Heater
(optional) installation instruction for details of
installation.
Rated Length (m)
For Heat
For
Elevation
Hydromodule
Unit
+ Tank
7
7
79
Accessories part
Max.
Min. Piping
Max. Piping
Length (m)
Length (m)
(m)
20
3
30
Qty.
1
Additional
Refrigerant
(g/m)
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquarea wh-uxz09ke5Aquarea wh-uxz12ke5