Panasonic AQUAREA WH-ADC0912K6E5AN Service Manual page 72

Hide thumbs Also See for AQUAREA WH-ADC0912K6E5AN:
Table of Contents

Advertisement

(A) Space Heating/Cooling Pipework
Connect Tank Unit Tube Connector
connector of Zone 1 Panel/Floor heater.
Connect Tank Unit Tube Connector
connector of Zone 1 Panel/Floor heater.
Connect Tank Unit Tube Connector
connector of Zone 2 Panel/Floor heater.
Connect Tank Unit Tube Connector
connector of Zone 2 Panel/Floor heater.
Failure to connect the tube appropriately might
cause the Tank Unit malfunction.
Refer below table for the rated flow rate of each
particular Outdoor Unit.
Model
Tank Unit
Outdoor Unit
WH-UXZ09KE5*
WH-
ADC0912K6E5AN
WH-UXZ12KE5*
(B) Domestic Hot Water Tank Pipework
It's strongly recommended to install an expansion
vessel (field supply) in the Domestic Hot Water
Tank circuit. Refer Typical Piping Installation
section to locate the expansion vessel.
Recommended pre-charge pressure of the
o
expansion vessel (field supply) = 0.35MPa
(3.5 bars)
In high water pressure or water supply is above
500kPa, please install the Pressure Reducing
Valve for water supply. If the pressure higher than
that, it might damage the Tank Unit.
A Pressure Reducing Valve (field supply) with
below specification is strongly advised to be
installed along the line of the tube connector
Tank Unit. Refer Typical Piping Installation section
to locate both of these valves.
Recommended Pressure Reducing Valve
specifications:
Set pressure: 0.35 MPa (3.5 bars)
Must connect a faucet to Tank Unit Tube
d
Connector
and main water supply, in order to
supply water with appropriate temperature for
shower or tap usage. Failure to do so might cause
scalding.
Failure to connect the tube appropriately might
causing the Tank Unit malfunction.
(C) Drain Elbow and Hose Installation
Fix the Drain Elbow 2 and Packing 3 to the
bottom of Drain Water Hole
Packing
3
Drain Elbow 2
a
to outlet
b
to inlet
j
to outlet
k
to inlet
Rated Flow Rate (l/min)
Cool
Heat
20.1
25.8
28.7
34.4
c
of
h
.
Use inner diameter 17 mm drain hose in the
market, fix to Drain Elbow 2 .
This hose must to be installed in a continuously
downward direction and in a frost-free
environment. Improper drain piping may cause
water leakage hence damage the furnitures.
If drain hose is long, use a metal support fixture
along the way to eliminate the wavy pattern of
drain tube.
Guide the drain hose to outdoor as illustrated.
Possible wall
Illustration of guide drain hose to outdoor
Do not insert this hose into sewage or drain pipe
that may generate ammonia gas, sulphuric gas
etc.
If necessary, use hose clamp to further tighten the
hose at drain hose connector to prevent leakage.
Water will drip from this hose, therefore the outlet
of this hose must be installed in an area where the
outlet cannot become blocked.
(D) Domestic Hot Water Tank Discharge (Drain
Tap) and Safety Relief Valve Pipework
Safety Relief Valve 0.8MPa (8 bars) incorporated
in Domestic Hot Water Tank.
Drain Tap and Safety Relief Valve discharge
fittings share the same drainage outlet.
Use R½" male connector for this drainage outlet
connection (Tube connector
Piping must always be installed in a continuously
downward direction. It must not be longer than
2m, with no more than 2 elbows, and must not
allow condensation to build up or freezing to
occur.
The pipe from this drainage outlet fitting must not
be shut off. The discharge must be freed.
The end of this pipework must be in such a way
so that the outlet is visible and can not cause any
damage. Keep away from electrical components.
It is recommended to fit a tundish into this
pipework. Tundish should be visible and
positioned away from frost environment and
electrical components.
72
Discharge below
fixed grating
Fixed grating
Trapped gulley
).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquarea wh-uxz09ke5Aquarea wh-uxz12ke5

Table of Contents