14.7 Indoor Back-Up Heater Control

14.7.1 Indoor Electric Heater Control
1
Normal Heating Mode
Heater On condition:
o
a. Heater switch is ON
b. After Heatpump thermo ON for Remote Control Set Delay Time mins
c. After water pump operate [3] mins
d. Outdoor air temperature < Outdoor set temperature for heater
e. When water outlet temperature < Water set temperature + Remote Control Heater ON Setting
f. [20] minutes since previous Backup heater Off
* When heatpump cannot operate due to error happens during normal operation, heater will go into
force mode automatic
* Heater need to operate during deice operation
Heater Stop Condition:
o
a. When outdoor set temperature > outdoor set temperature + [+2°C] for continuous 15 secs OR
b. When water out temp > water set temperature + Remote Control Heater OFF Setting for continuous 15
secs OR
c. Heater switch is Off OR
d. Heatpump thermo-off or OFF condition
2
Force Heater Mode
Heater On condition:
o
a. After water pump operate [3] mins
b. When water outlet temperature < water set temperature + Remote Control Heater ON Setting
c. [20] minutes since previous Backup heater Off
Heater Stop condition
o
a. Force mode off OR
b. When water outlet temperature > water set temperature + Remote Control Heater OFF Setting for
continuous 15 secs
* Do not operate heater at the following situation
1
Water outlet temperature sensor, and water inlet sensor abnormal
2
Flow switch abnormal
3
Circulation pump stop condition