14.1.10 Heat + Tank Mode Operation
1
3 ways valve control:
3 ways valve switch to room side during room heat-up interval and switch to tank side during tank heat-
o
up interval. Both modes will switch alternately. Tank mode is the initial running mode of Heat + Tank
mode.
2
Heat pump operation control:
During room heat-up interval
o
 Follow normal heating operation.
Switching to tank side depends to below cases:
Case 1:
[Previous switch from tank interval to room interval due to thermo OFF]
 Switch to tank heat-up interval when Tank temp < Tank thermos ON temp (Room heat-up interval
ends)
Case 2:
[If heating operation at room side is less than 30 minutes and switch to tank side 3 times
consecutively]
 Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND Tank
temperature < Tank thermo ON temperature.
Case 3:
[Previous switch from tank interval to room interval due to tank interval timer is complete]
 Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND tank
temperature < Tank thermo ON temperature.
During Tank heat-up interval
o
 Tank interval is the first mode running when heat + tank mode is select.
 Switch to room interval only when tank achieve tank thermo OFF OR tank heat-up interval timer is
complete.
 Heat pump operates according to normal tank mode operation.
3
Room heater control:
During heating heat-up interval
o
 Follow normal room heater control operation.
4
Tank heater control:
During heating heat-up interval
o
 Internal tank heater will not function under heating heat-up interval.
During tank heat-up interval
o
 Internal tank heater will turn ON after heat pump thermo off to boil tank temperature to tank set
temperature.
2 ways valve control is open
o
Indoor water pump control:
o
 Indoor water pump always turn ON if room heat pump thermo ON OR Tank thermo ON.
14.1.11 Cool + Tank Mode Operation
1
3 ways valve control:
3 ways valve switch to room side during room cooling interval and switch to tank side during tank heat-
o
up interval. Both mode will switch alternately. Tank mode is the initial mode of cool + tank mode.
2
Heat pump operation control:
During room heat-up interval
o
 Follow normal cooling operation.
Switching to tank side depends to below cases:
Case 1:
[Previous switch from tank interval to room interval due to thermo OFF]
 Switch to tank heat-up interval when Tank temperature < Tank Thermo ON temperature (Room
interval will ends)
Case 2:
[If cooling operation at room side is less than 30 minutes and switch to tank side for 3 times
consecutively]
139