18.5.37 Low Discharge Superheat (F29)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature
sensor are used to determine sensor error.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty outdoor unit PCB (main).
4
Faulty High Pressure Switch
5
Refrigerant shortage (refrigerant leakage).
Abnormality Judgment:
1 times occurrence within 2550 minutes.
Troubleshooting:
Outdoor Pipe / Outdoor Defrost Sensor
Characteristic
30
25
20
15
10
5
0
-10
0
10
20
30
Temperature (°C)
Check the CN-DIS & CN-TH1 connection:
- Turn OFF the power.
- Check the connector connection.
- Is the CN-DIS & CN-TH1 connector normal?
- Measured the resistance of the sensor, is
the measured resistance matches the value
specified in its characteristic chart?
Check Refrigeration Cycle Pressure.
Is the refrigerant cycle pressure normal?
- Defect in Outdoor Unit PCB.
- Replace the Outdoor Unit PCB.
40
50
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Yes
Yes
227
No
- Replace the temperature
Sensor.
No
- Recharge Gas.
Compressor Tank / Compressor Discharge Sensor
Characteristic
350
300
250
200
150
100
50
0
-10
0
10
20
30
40
Temperature (°C)
50