Indoor Back-Up Heater Control; Tank Booster Heater Control - Panasonic WH-SDF09C3E5 Service Manual

Air-to-water heatpump
Hide thumbs Also See for WH-SDF09C3E5:
Table of Contents

Advertisement

13.9

Indoor Back-Up Heater Control

13.9.1 Indoor Electric Heater Control
1
Normal Heating Mode
Heater On condition:
o
a. Heater switch is ON
b. After Heatpump thermo ON for [30] mins
c. After water pump operate [9] mins
d. Outdoor air temperature < Outdoor set temperature for heater
e. [20] minutes since previous Backup heater Off
* When heatpump cannot operate due to error happens during normal operation, heater will go into
force mode automatic
* Heater need to operate during deice operation
f. When water outlet temperature < Water set temperature + [-8°C] (check water out temperature
before ON heater 3 and check also water out temperature after heater delay timer before ON heater
2 and 1)
Heater Stop Condition:
o
a. When outdoor set temperature > outdoor set temperature + [+2°C] for continuous 15 secs OR
b. When water out temp> water set temperature + [-2°C] for continuous 15 secs OR
c. Heater switch is Off OR
d. Heat pump thermo-off or OFF condition
2
Force Heater Mode
Heater On Condition:
o
a. After water pump operate [9] mins
b. When water outlet temperature < water set temperature + [-8°C]
c. [20] minutes since previous Backup heater Off
Heater Stop condition
o
a. Force mode off OR
b. When water outlet temperature > water set temperature + [-2°C] for continuous 15 secs
* Do not operate heater at the following situation
1
Water outlet temperature sensor, and water inlet sensor abnormal
2
Flow switch abnormal
3
Circulation pump stop condition
4
During Heatpump switch to tank side

13.10 Tank Booster Heater Control

13.10.1 Tank Booster Heater Control
Heating operation condition:
1
Booster heater Turn On condition:
After BOOSTER HEATER DELAY TIMER fulfill during heat pump startup time in tank mode, or during
o
switching from heating heat-up interval to tank heat-up interval in heat + tank mode (heating priority not
set).
Tank temperature < tank set temperature + [-5°C],
o
20 minutes since previous heater off.
o
* BOOSTER HEATER DELAY TIMER is clear when tank heat-up interval end.
77