Model Specifications

Table 10. Electrical Input (Continued)
Model
Table 11. Electrical Input Connections
Model
9PX6K-L
Table 12. Electrical Output
All Models
Voltage Regulation
Efficiency
Frequency Regulation
Nominal Output
Frequency
Output Overload
Output Overload ( Bypass Mode )
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Ratio
40
Eaton 9PX Lithium-Ion User Guide DPD-9PX2206—Rev 01
Default Input
(Voltage/Max Current)
Frequency Range
Bypass Voltage Range
Noise Filtering
Normal Mode
±1%
> 98% (High Efficiency mode)
>93%
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
200*/208*/220*/230*/240V (voltage configurable)
6000VA* 4500/5400W*
50 or 60 Hz, autosensing or configurable as a frequency converter
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 500ms
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online Mode: 0ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Up to 0.9
Up to 3:1
Input Nominal Voltages
50Hz : 40-60Hz before transfer to battery
60Hz : 50-70Hz before transfer to battery
-20% / +15% of nominal value (default)
MOV for normal and common mode noise
Input Connection
L6-30P cord or Hardwired

Battery Mode

±1%
> 91%
±0.5% of auto-selected nominal
frequency
Input Voltage Window at
Rated Load