Unigas E115X Installation Manual page 93

Table of Contents

Advertisement

X52
Terminal
Connection symbol
group
Temperature / pressure controller
X60
X61
X62
X63
(functional earth)
PIN4
x
AC power supply from transformer to
LMV5... system
PIN3
x
PIN2
x
Reference ground (PELV)
AC power supply from transformer to
LMV5... system
PIN1
x
Description of connection termi- nals
Functional earth for shield connec- tion
PIN5
x
PIN4
x
Reference ground
Temperature sensor input Pt / LG- Ni
1000
PIN3
x
Line compensation temperature
sensorPT100
PIN2
x
PIN1
x
Temperature sensor input PT100
Functional earth for shield connec- tion
PIN5
x
PIN4
x
Reference ground
Current input for temperature / pressure
signal 0/4...20 mA
PIN3
x
Voltage input for temperature / pressure
signal DC 0...10 V
PIN2
x
Power supply for temperature / pressure
transmitter
PIN1
x
Functional earth for shield connec- tion
PIN5
x
PIN4
x
Reference ground
PIN3
x
Current input for setpoint or load
PIN2
x
Voltage input for setpoint or load
Power supply for setpoint changeo- ver
PIN1
x
Functional earth for shield connec- tion
PIN3
x
PIN2
x
Reference ground
Current output for burner(LOAD
OUTPUT)
PIN1
x
AC 12 V +10 % / -15 %, 50...60 Hz
AC 12 V +10 % / -15 %, 50...60 Hz
Electrical rating
DC 0/4...20 mA
DC 0...10 V
approx. DC 20 V Max. 25 mA
DC 0...20 mA
DC 0...10 V
approx. DC 24 V Max. 2 mA
DC 4...20 mA, RLmax = 500 £[

Advertisement

Table of Contents
loading

This manual is also suitable for:

E150xE180x

Table of Contents