Table 15. The PowerEdge MX760c thermal restriction matrix (continued)
Configuration
Adjacent Sled Condition
Support
Front Storage Type
6458Q
350W
Mem
256 GB
13.2W,
ory
RDIMM
2 DPC
(Syst
4800
em Is
128 GB
9.7W,
Air
RDIMM
2 DPC
Cool
4800
ed,
No
64 GB
8.5W,
Liqui
RDIMM
2 DPC
d)
4800
32 GB
4.2W,
RDIMM
2 DPC
4800
PCI
Mezzanine card,
Card
Tier2, ≤ 30 W
Mini Mezzanine
card
Note
* Optimized sled condition is to recommend the nearby sleds population with same storage configuration or sled blank
s
for thermally optimization by air cooling.
** Wider HPR heatsink is required for > 225W CPUs
*** Max DIMM count support for wider HPR heatsink is 24 pcs depended on DIMM population guidance.
**** Liquid cooling solution can support all CPU SKUs, but is limited in 4 drives BP and E3.s BP configurations due to
ME constrain
Extended ambient restrictions
ASHRAE A3 environment
● Do not perform a cold startup below 5°C
● The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
● With Air Cooling Solution, Higher wattage processors, Thermal Design Power (TDP) > 185 W are not supported.
● With Liquid Cooling Solution, all processors are supported.
● Non-Dell qualified peripheral cards or peripheral cards greater than 30 W are not supported.
● PCIe SSD is not supported.
● 128 GB or higher capacity RDIMM is not supported.
● E3.s drive is not supported.
ASHRAE A4 environment
● Do not perform a cold startup below 5°C.
● The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
● With Air Cooling Solution, Higher wattage processors, Thermal Design Power (TDP) > 165 W are not supported.
● With Liquid Cooling Solution, all processors are supported.
24
Technical specifications
6 x 2.5-inch BP
6 x 2.5-inch BP
Not Limited
Optimized*
SAS
NVMe
SAS
drive
drive
drive
Not Supported
Not Supported
30°C
30°C
30°C
35°C
35°C
35°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
4 x 2.5-inch BP
Not Limited
NVMe
SAS
NVMe
drive
drive
drive
Liquid Cooling
Required
30°C
35°C
35°C
35°C
35°C
35°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
8 x E3.s BP
Diskless in 4 x
2.5" BP
Not Limited
Not Limited
E3 drive
No drive
Liquid Cooling
Liquid Cooling
Required
Required
35°C
35°C
35°C
35°C
35°C
35°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
45°C
35°C
35°C
45°C
45°C
45°C
45°C