Beckhoff EL2904 Operating Instructions Manual page 30

Twinsafe output terminal with 4 fail-safe outputs
Hide thumbs Also See for EL2904:
Table of Contents

Advertisement

Operation
Parameter overview
PrmName
Standard outputs
active
Current
measurement active
Testing of outputs
active
Error acknowledge
active
Store Code
Project CRC
28
Meaning
In addition the output can be switched off from the
standard PLC. The safe output is linked with the
standard logic signal AND.
Current measurement for the outputs is activated
Test pulses for the outputs are activated
True:
Terminal errors lead to a reset of the TwinSAFE
connection (error code 14 (0x0E)). This error
code is shown in the diagnostic data for the
connection until the user acknowledges it via
ErrAck in the TwinSAFE group.
False (Default):
Terminal errors can only be reset by switching the
power supply off and back on again.
This parameter is required for the TwinSAFE
Restore Mode
This parameter is required for the TwinSAFE
Restore Mode
Values
true / false
true / false
true / false
true / false
0x0000
0x0000
EL2904