130 Parameters
No.
Name/Value
23.13
Deceleration time
1
0.000...
1800.000 s
Description
Defines the time required for the speed to
change from the speed defined by parameter
46.01 Speed scaling
speed) to zero.
Maximum
If the speed reference decreases slower than the
set deceleration rate, the motor speed will follow
the reference.
If the reference changes faster than the set
deceleration rate, the motor speed will follow the
deceleration rate.
If the deceleration rate is set too short, the drive
will automatically prolong the deceleration in
order not to exceed drive torque limits (or not to
exceed a safe DC link voltage).
Notes:
• Applicable only for ramp stop condition. For all
normal reference changes (except pump
cleaning operation, as it has it's own ramp
times) from MPPT reference, zero deceleration
ramp time is considered.
• If a short deceleration time is needed for a high
inertia application, the drive should be
equipped with braking equipment such as a
brake chopper and brake resistor.
Deceleration time 1.
(not from parameter
Def/
FbEq16
20.000
30.12
10 = 1 s