Contents Of The Fieldbus Control Word - ABB ACQ80 Firmware Manual

Standard program control
Table of Contents

Advertisement

Scaling of actual values
The actual values are scaled as defined by parameters
scaling is in use depends on the setting of parameters
and
50.08 FBA A actual 2 type
Fieldbus

Contents of the fieldbus Control word

The upper case boldface text refers to the states shown in the state diagram
(page
376).
Bit
Name
0
Off1 control
1
Off2 control
2
Off3 control
3
Run
4
Ramp out zero
Fieldbus control through a fieldbus adapter 373
(see page 211).
99.09
(with motor nominal speed)
20000
99.08
(with motor nominal frequency)
46.03
(with torque reference)
10000
46.04
(with power reference)
0
0
-(46.03) (with torque reference)
-10000
-(46.04) (with power reference)
-(99.09) (with motor nominal speed)
-20000
-(99.08) (with motor nominal frequency)
Value STATE/Description
1
Proceed to READY TO OPERATE.
0
Stop along currently active deceleration ramp. Proceed to OFF1
ACTIVE; proceed to READY TO SWITCH ON unless other
interlocks (OFF2, OFF3) are active.
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to a stop.
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON INHIBITED.
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive parameter.
Proceed to OFF3 ACTIVE; proceed to SWITCH-ON INHIBITED.
WARNING: Ensure motor and driven machine can be
stopped using this stop mode.
1
Proceed to OPERATION D.
Note: Run enable signal must be active; see drive documentation.
If the drive is set to receive the Run enable signal from the
fieldbus, this bit activates the signal.
0
Inhibit operation. Proceed to OPERATION INHIBITED.
1
Normal operation. Proceed to RAMP FUNCTION GENERATOR:
OUTPUT D.
0
Force Ramp function generator output to zero. The drive will
immediately decelerate to zero speed (observing the torque
limits).
and 46.04; which
46.03
50.07 FBA A actual 1 type
Drive