No.
Name/Value
40.70
Compensated
setpoint
-21474836.48...
21474835.20 PID
unit 1bar
40.71
Set 1
compensation
input source
Not selected
Reserved
Internal
setpoint
AI1 scaled
AI2 scaled
Reserved
Freq in scaled
AI1 percent
Description
Compensated setpoint determined for the input
specified by parameter
input
source.
The determination of the compensated setpoint
is based on the curve specified by points (x1, y1),
(x2, y2) and the non-linearity of the curve
specified with parameters 40.71...40.76. The
compensated setpoint curve will be a mixture of
a straight line between the points and a squared
line between the points:
y
x1,y1
x
= value from
40.71 Set 1 compensation input
source
y
=
40.70 Compensated setpoint
a =
40.76 Set 1 compensation non-linearity
Compensated setpoint curve = a * squared
Compensated setpoint value.
Selects the source for set 1 compensation input.
None.
Internal setpoint.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
12.101 AI1 percent value
40.71 Set 1 compensation
a = 0
a = 1
(see page 110).
(see page 112).
(see page 107).
(see page 114).
Parameters 201
Def/
FbEq16
-
x2,y2
x
1 = 1 PID
unit 1bar
Not
selected
0
1
2
3
4
5...9
10
11