ABB ACQ80 Firmware Manual page 191

Standard program control
Table of Contents

Advertisement

No.
Name/Value
40.03
Process PID
setpoint actual
-200000.00...
200000.00
40.04
Process PID
deviation actual
-200000.00...
200000.00
40.06
Process PID
status word
Bit
Name
0
PID active
1
Setpoint frozen 1 = Process PID setpoint frozen.
2
Output frozen
3
PID sleep mode 1 = Sleep mode active.
4
Sleep boost
5
Reserved
6
Tracking mode 1 = Tracking function active.
7
Output limit
high
8
Output limit
low
9
Reserved
10
PID set
11
Reserved
12
Internal
setpoint active
13...15 Reserved
0b0000...
0b1111
40.07
Process PID
operation mode
Off
On
Description
Shows value of process PID setpoint after source
selection, mathematical function limitation and
ramping.
This parameter is read-only.
Setpoint for process PID controller.
Shows process PID deviation. By default, this
value equals setpoint - feedback, but deviation
can be inverted by parameter
deviation
inversion.
This parameter is read-only.
PID deviation.
Shows status information on process PID
control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID controller output frozen.
1 = Sleep boost active.
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
1 = Internal setpoint active (see par. 40.16...40.16)
Process PID control status word.
Activates/deactivates process PID control.
Note: Process PID control is only available in
external control; see section
(page 35).
external control
Process PID control inactive.
Process PID control active.
Parameters 191
40.31 Set 1
Local control vs.
Def/
FbEq16
-
1 = 1
-
1 = 1
0b0000
1 = 1
Off
0
1