Page 1
LUNA2000-100KTL-M1 Smart Power Control System User Manual Issue Date 2023-01-10 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
Purpose This document describes the installation, electrical connections, commissioning, maintenance, and troubleshooting of the LUNA2000-100KTL-M1 Smart Power Control System (also referred to as Smart PCS). Before installing and operating the Smart PCS, ensure that you are familiar with the features, functions, and safety precautions provided in this document.
Page 4
LUNA2000-100KTL-M1 Smart Power Control System User Manual About This Document Change History Changes between document issues are cumulative. The latest document issue contains all updates made in previous issues. Issue 02 (2023-01-10) Updated 1 Safety Information. Updated 4.3 Pre-installation Checks.
LUNA2000-100KTL-M1 Smart Power Control System User Manual Contents Contents About This Document........................ ii 1 Safety Information........................1 1.1 Personal Safety..................................2 1.2 Electrical Safety..................................4 1.3 Environment Requirements..............................7 1.4 Mechanical Safety................................... 8 2 Product Overview........................13 2.1 Model......................................13 2.2 Functions and Features............................... 14 2.3 Appearance.....................................
Page 6
LUNA2000-100KTL-M1 Smart Power Control System User Manual Contents 5.8 Connecting FE Communications Cables........................43 5.9 Closing Maintenance Compartment Doors......................... 46 5.9.1 Closing the DC Maintenance Compartment Door....................46 5.9.2 Closing the AC Maintenance Compartment Door....................47 6 Power-On Commissioning....................48 6.1 Checking Before Power-On..............................50 6.2 Powering On the Smart PCS.............................
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information Safety Information Statement Before transporting, storing, installing, operating, using, and/or maintaining the equipment, read this document, strictly follow the instructions provided herein, and follow all the safety instructions on the equipment and in this document. In this document, "equipment"...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information ● The equipment is installed or used in environments that do not comply with international, national, or regional standards. ● You fail to follow the operation instructions and safety precautions on the product and in the document.
Page 9
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information WARNING During operations, wear personal protective equipment such as protective clothing, insulated shoes, goggles, safety helmets, and insulated gloves. Figure 1-1 Personal protective equipment General Requirements ● Do not stop protective devices. Pay attention to the warnings, cautions, and related precautionary measures in this document and on the equipment.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information – Trained personnel: personnel who are trained in technology and safety, have required experience, are aware of possible hazards on themselves in certain operations, and are able to take protective measures to minimize the hazards on themselves and other people ●...
Page 11
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information CA UTION Do not route cables behind the air intake and exhaust vents of the equipment. General Requirements ● Follow the procedures described in the document for installation, operation, and maintenance. Do not reconstruct or alter the equipment, add components, or change the installation sequence without permission.
Page 12
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information ● Do not use solvents such as water, alcohol, or oil to clean electrical components inside or outside of the equipment. Grounding ● Ensure that the grounding impedance of the equipment complies with local electrical standards.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information to cable damage, which affects the current-carrying capacity and temperature rise. 1.3 Environment Requirements D ANGER Do not expose the equipment to flammable or explosive gas or smoke. Do not perform any operation on the equipment in such environments.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information connectors to or removing connectors from signal ports connected to outdoor facilities, working at heights, performing outdoor installation, and opening doors) in harsh weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
Page 15
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information WARNING Do not drill holes into the equipment. Doing so may affect the sealing performance and electromagnetic containment of the equipment and damage components or cables inside. Metal shavings from drilling may short-circuit boards inside the equipment.
Page 16
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information ● When moving a heavy object, be aware of the workbench, slope, staircase, and slippery places. When moving a heavy object through a door, ensure that the door is wide enough to move the object and avoid bumping or injury.
Page 17
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information ● If a single ladder is used, ensure that the wider end of the ladder is at the bottom, and take protective measures to prevent the ladder from sliding. ●...
Page 18
LUNA2000-100KTL-M1 Smart Power Control System User Manual 1 Safety Information Drilling Holes ● Obtain consent from the customer and contractor before drilling holes. ● Wear protective equipment such as safety goggles and protective gloves when drilling holes. ● To avoid short circuits or other risks, do not drill holes into buried pipes or cables.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Product Overview 2.1 Model Model Number Figure 2-1 Model Table 2-1 Model number description Meaning Description Product family LUNA2000: Smart PCS name Power level 100K: The power level is 100 kW.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Figure 2-2 Position of the model label on the external package (1) Position of the model label 2.2 Functions and Features Functions ● The Smart PCS implements rectification and inversion through a three-phase three-level converter.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Figure 2-3 Power grid type 2.3 Appearance Appearance Figure 2-4 Appearance (1) AC maintenance (2) Communications (3) Panel compartment cable hole (FE) (4) Protective cover (5) DC maintenance (6) LED indicator...
Page 22
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview (13) USB port (USB) (14) DC power cable hole Note [1]: The security Torx wrench is delivered with the device and is tied to the bracket on the top of the chassis. Remove the security Torx wrench from the bracket and keep it safe.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Label Name Description Delayed discharge ● There may be a risk of shock when the device is powered on. Only qualified and trained electrical technicians should install and operate the device.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Figure 2-6 Circuit diagram 2.4.2 Working Modes The Smart PCS can work in standby, operating, or shutdown mode. Figure 2-7 Working modes Table 2-3 Working mode description Working Description Mode...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Working Description Mode Operating In operating mode: ● The Smart PCS controls charge and discharge based on system commands. ● The Smart PCS enters Shutdown mode after detecting a fault or receiving a shutdown command.
Page 26
LUNA2000-100KTL-M1 Smart Power Control System User Manual 2 Product Overview Table 2-4 0.8 MWh/400 kW standard configurations Item Recommended Model/ Quantity Source Specifications Smart String LUNA2000-200KWH-2H1 Purchased Energy Storage from the System Company (ESS for short) Smart PCS LUNA2000-100KTL-M1 Purchased...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 3 Storage Storage NO TICE ● Do not transport devices without appropriate packaging. ● Do not tilt the packaging or place it upside down. If the Smart PCS is not installed immediately, it should be stored according to the requirements outlined in this section.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Installation 4.1 Environment Requirements Basic Requirements ● Do not install the Smart PCS in working or living areas. ● If the device is installed in public places (such as parking lots, stations, and factories) other than working and living areas, install a protective net outside the device and erect a warning sign to isolate it.
Page 30
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation NO TE ● Class C environment: Outdoor areas more than 500 m away from the sea. If a site is near a pollution source, it must be 1500–3000 m away from heavy pollution sources, such as smelteries, coal mines, and thermal power plants;...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Installation Angle Requirements Figure 4-2 Installation angle 4.2 Preparing Tools Before installation, the following tools need to be prepared. Installation Tools Hammer drill Drill bit (Ф14 mm Insulated torque Phillips insulated and Ф16 mm)
Page 32
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Wire strippers Rubber mallet Utility knife Diagonal pliers RJ45 crimping tool Hydraulic pliers Cable cutter Vacuum cleaner Steel measuring Level Cable tie Marker tape Heat-shrink tubing Heat gun Step ladder Digital multimeter...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Crane Lifting rope Hoisting capability Length of the ≥ 1 t; operation lifting rope ≥ 1.8 m radius ≥ 2 m Personal Protective Equipment (PPE) Goggles Dust mask Insulated shoes Insulated gloves...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation NO TE You are advised to install the device within 24 hours of removing the outer packing. Unpacking the Device Step 1 Use diagonal pliers to cut the packing tape, and use a utility knife to slice the tape along the gaps in the packaging.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Figure 4-4 Hoisting ----End 4.5 Installing the Smart PCS Prerequisites The mounting brackets (including M12 bolt assemblies) are delivered with the device. Mounting Bracket Dimensions The Smart PCS mounting bracket has four groups of tapped holes, with each group containing four tapped holes.
Page 37
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Figure 4-5 Hole dimensions Installation Procedure Step 1 Install the mounting bracket. Figure 4-6 Installing the mounting bracket NO TE If the bolt length does not meet the installation requirements, prepare M12 bolts and use them together with the delivered M12 nuts.
Page 38
LUNA2000-100KTL-M1 Smart Power Control System User Manual 4 Installation Figure 4-7 Installing mounting ears Step 3 Install the device on the mounting bracket. Step 4 Tighten the two screws at the bottom of the device. Figure 4-8 Installing the device...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Electrical Connections 5.1 Precautions D ANGER ● Before connecting cables, ensure that the DC and AC switches on the Smart PCS and all switches connecting to it are set to the OFF position. Otherwise, the high voltage of the device may result in electric shocks.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections NO TE The cable colors shown in the electrical connection diagrams provided in this chapter are for reference only. Select cables in accordance with local cable specifications (green-and- yellow cables are only used for PE). The factors that affect cable selection include the rated current, cable type, routing mode, ambient temperature, and maximum expected line loss.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections 5.3 Connecting the Ground Cable NO TICE ● The grounding should comply with local electrical safety regulations. ● It is recommended that the Smart PCS be connected to a nearby ground point.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections 5.4 Opening the Maintenance Compartment Doors NO TICE ● Do not open the Smart PCS panel. ● Before opening the maintenance compartment door of the Smart PCS, turn off the external switches on the AC and DC sides.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-3 Removing accessories from the DC maintenance compartment (1) Spare screws on the door panel of (2) Crimping module the maintenance compartment ----End 5.4.2 Opening the AC Maintenance Compartment Door Step 1 Open the AC maintenance compartment door.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-5 Removing accessories from the AC maintenance compartment (1) Spare screws on the door panel of (2) Crimping module the maintenance compartment ----End 5.5 Replacing the Crimping Module Procedure NO TE ●...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-7 (Optional) Replacing the crimping module (on the AC side) ----End Follow-up Procedure Use scissors to cut off the joints of the rubber rings in order to remove them.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Procedure NO TICE ● The cable outer diameter can be measured using the ruler sticker in the maintenance compartment. ● Ensure that the cable jacket is in the maintenance compartment.
Page 47
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections exception occurs, select a proper overcurrent protection device in compliance with local power distribution regulations. WARNING ● Do not connect loads between a PCS and an AC switch that directly connects to the PCS.
Page 48
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-10 Single-core cable connections Figure 5-11 Multi-core cable connections NO TE It is recommended that the stripped length of the L2 wire be 15 mm shorter than that of the L1 or L3 wire.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections ----End 5.8 Connecting FE Communications Cables NO TICE ● The Smart PCS is connected to the SmartModule through FE communications cables. Ensure that the FE ports on the two ends are connected to GE2 and GE3 of the SmartModule.
Page 50
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Communication Port Description Figure 5-12 Port description (1) Network port 2 (FE2) (2) Network port 1 (FE1) (3) Communications port (COM) (reserved) Figure 5-13 Communications cable connection Procedure Step 1 Remove an appropriate length of the insulation layer from the shielded network cable using a wire stripper.
Page 51
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections (1) Shielded plug (2) Plastic housing (3) Coupling nut (4) Seal ring (5) Sealing nut Step 3 Line up the exposed wires of the network cable in sequence and connect them to the corresponding pins in the plug.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-19 Connecting FE communications cables (1) White-and- (2) Orange (3) White-and- (4) Blue orange green (5) White-and-blue (6) Green (7) White-and- (8) Brown brown ----End 5.9 Closing Maintenance Compartment Doors NO TICE ●...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 5 Electrical Connections Figure 5-20 Closing the DC maintenance compartment door ----End 5.9.2 Closing the AC Maintenance Compartment Door Step 1 Adjust the support bar, close the maintenance compartment door, and tighten the two screws on the door.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Power-On Commissioning ● Ensure that all the preceding items are checked and meet requirements before power-on. ● The Smart PCS can be commissioned using the SmartLogger WebUI or the SUN2000 app. You can manage multiple devices on the SmartLogger WebUI.
Page 55
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Table 6-1 LED indicators Category Indicator Status (Blinking Description Fast: On for 0.2s and then Off for 0.2s; Blinking Slowly: On for 1s and then Off for 1s) DC indication...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning NO TE ● If the DC and running indicators are not blinking red fast and the fault/maintenance indicator is steady red, you need to replace the faulty components or the entire device.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning 6.2 Powering On the Smart PCS Precautions D ANGER ● Wear insulated gloves and use insulated tools to prevent electric shocks or short circuits. NO TICE ● Before turning on the AC switch between the Smart PCS and the power grid, check whether the AC voltage is within the required range using a multimeter.
Page 58
Smart PCS through the WLAN module. NO TICE ● The USB-Adapter2000-C WLAN module is supported. ● The mobile phone operating system must be Android 5.0 or later. ● Huawei and Samsung phones are recommended. Figure 6-2 WLAN module connection (A) Smart PCS (B) WLAN module...
● The parameter names, value ranges, and default values are subject to change. Downloading the App SUN2000 app: Access Huawei AppGallery, search for SUN2000, and download the app installation package. Alternatively, scan one of the QR codes below to download the app installation package.
Page 60
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Figure 6-3 Selecting a connection mode Step 2 Select the login user and enter the login password. The main menu page is displayed. NO TICE ● When you log in to the system for the first time, set the login password. To ensure account security, change the password periodically and do not forget the new password.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Figure 6-4 Login NO TE Set the correct grid code for the Smart PCS based on regions and application scenarios. ----End 6.5 Setting Parameters 6.5.1 Setting Grid Parameters Procedure Step 1 Choose Settings > Grid parameters to set grid parameters.
Page 62
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Parameter Description frequency level Specifies the frequency level of the power grid. Output mode Specifies supported power grid types. Isolation Specifies the device grounding status at the DC side and the connection to the power grid.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Parameter Description Grid reconnection According to the standards of certain countries and regions, frequency lower limit grid reconnection is not allowed when the grid frequency is (Hz) below the minimum grid frequency for grid reconnection.
Page 64
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description 10-min Specifies the 10-minute overvoltage overvoltage protection duration. protection time (ms) Overvoltage Level-M Specifies the level-N grid protection overvoltage overvoltage protection threshold. protection threshold (V) Level-M Specifies the level-N grid overvoltage overvoltage protection duration.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning 6.5.3 Setting Feature Parameters Procedure Step 1 Choose Settings > Feature parameters to set feature parameters. ----End Parameters Category Parameter Description Remarks Communication Communication If this parameter is set to...
Page 66
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Active power Specifies the active power This parameter is threshold when threshold as a fixed value. displayed when the communication protection in the fails (kW) case of...
Page 67
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Shutdown Shutdown Specifies the power change gradient gradient (%/s) rate when the device shuts down. Hibernate at Hibernate at The device performs the night night monitoring function at night.
Page 68
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks HVRT gradient During HVRT, the device must generate positive-sequence reactive power to support the power grid. This parameter is used to set the positive- sequence reactive power generated by the device.
Page 69
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks LVRT gradient During LVRT, the device must generate positive-sequence reactive power to support the power grid. This parameter is used to set the positive- sequence reactive power generated by the device.
Page 70
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Threshold of When Zero current due to LVRT zero- power grid fault is enabled, current mode if the power grid voltage is less than the value of...
Page 71
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks VRT active Specifies the recovery rate power recovery when the active current gradient recovers to the value at the moment before FRT. Zero current due Specifies whether to enable...
Page 72
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Execution delay Specifies the effective delay of frequency- time of overfrequency-caused based active derating when the frequency power derating reaches the trigger frequency of overfrequency-caused derating.
Page 73
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Delay of Delay from the time when underfrequency- the underfrequency-caused caused power power raising function is raising triggered to the time when the function takes effect...
Page 74
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks VSG inertia time Specifies the time required for constant (s) the virtual rotor of the virtual synchronous generator to reach the rated speed from the static state under the rated torque.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning 6.5.4 Setting Power Adjustment Parameters Procedure Step 1 On the home screen, tap Power adjustment to go to the parameter setting screen. ----End Parameters Category Parameter Description Remarks Remote control...
Page 76
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Q-U characteristic Specifies the reactive power curve mode compensation mode of the device output. Delay for Q-U Specifies the delay time for Q-U characteristic curve adjustment.
Page 77
LUNA2000-100KTL-M1 Smart Power Control System User Manual 6 Power-On Commissioning Category Parameter Description Remarks Reactive power Specifies the voltage threshold compensation for exiting reactive power (cosφ-P) exit compensation based on the voltage curve. Reactive power Specifies the adjustment time for...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Device Maintenance D ANGER ● Wear insulated gloves and use insulated tools to prevent electric shocks or short circuits. WARNING ● Before performing maintenance, power off the equipment, follow the instructions on the delayed discharge label, and wait for a period of time as specified to ensure that the equipment is not energized.
Page 79
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Table 7-1 Maintenance checklist Check Item Check Method Maintenance Interval ● Cleanness of ● Check whether there is dust on Once every 6 to 12 the air inlet the air inlet and outlet. If...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance NO TICE After cleaning is complete, reinstall the air inlet baffle. Tighten the screws to a torque of 1.2 N·m. Removing the Air Outlet Protective Cover Figure 7-2 Removing the protective cover NO TICE After cleaning is complete, reinstall the air outlet protective cover.
Page 81
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Step 2 Deliver a shutdown command on the SUN2000 app, SmartLogger, or management system. Step 3 Turn off the AC switch between the Smart PCS and the grid. Step 4 Open the AC maintenance compartment door, install a support bar, and use a multimeter to measure the voltage between the AC terminal block and the ground.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance 7.3 Replacing a Fan CA UTION ● Before replacing a fan, power off the Smart PCS. ● When replacing a fan, use insulation tools and wear PPE. NO TE If the fan gets stuck when being pulled or pushed, slightly lift it.
Page 83
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Figure 7-6 Pulling out fan tray (2) Step 4 Remove cable ties from the faulty fan. ● Fan 1 is faulty. Figure 7-7 Removing cable ties from fan 1 ●...
Page 84
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Figure 7-10 Removing the fan Step 6 Install a new fan (fan 1 is used as an example). Figure 7-11 Installing a new fan Step 7 Bind the fan cables.
Page 85
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Step 8 Push in the fan tray until the fan baffle plate is flush with the Smart PCS. Figure 7-15 Pushing in the fan tray Step 9 Connect the cables correctly according to the cable labels, and then bind the cables.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance 7.4 Replacing the Smart PCS Context The device enclosure is severely damaged or the device hardware is faulty due to external forces. Procedure Step 1 Deliver a shutdown command on the SUN2000 app, SmartLogger, or management system.
Page 87
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Step 2 Upgrade software of the new Smart PCS. Ensure that the software version of the new Smart PCS is the same as that of other Smart PCSs on site.
Page 88
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Figure 7-20 Energy yield calibration Step 6 (Optional) If a third-party NMS that complies with the IEC 104 protocol is connected, choose Settings > IEC104, and ensure that the teleindication, telemetering, telecontrol, and teleadjust signal numbers of the new Smart PCS on all tab pages under IEC104 are the same as those of the faulty Smart PCS.
Page 89
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance NO TE ● During the process of Search for Device, do not perform upgrade operations (such as upgrading through the app, management system, or WebUI). ● When you click Search for Device, cable connections (DC and AC) will be checked before device search (not applicable to third-party devices), and device addresses will be automatically allocated.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 7 Device Maintenance Figure 7-23 Deleting a device ----End 7.5 Disposing of the Smart PCS If the Smart PCS reaches the end of its service life, dispose of the device according to local regulations for the disposal of electrical equipment.
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Reference Alarm severities are defined as follows: ● Major: The Smart PCS is faulty or the external environment is abnormal. As a result, the output power decreases or the grid-tied power generation is stopped.
Page 92
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2006 DC Short- Major Cause ID = 1 Power off the device (turn off Circuited or the AC switch and DC switch, The DC bus of the device is...
Page 93
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2033 Grid Major Cause ID = 1 1. If the alarm occurs Undervolta occasionally, the power grid The grid voltage is below the...
Page 94
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2035 Grid Major Cause ID = 1 1. If the alarm occurs Voltage occasionally, the power grid The difference between grid Imbalance may be abnormal phase voltages exceeds the temporarily.
Page 95
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2037 Grid Major Cause ID = 1 1. If the alarm occurs Underfrequ occasionally, the power grid Power grid exception: The ency may be abnormal power grid frequency is lower temporarily.
Page 96
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2040 Major Cause ID = 1 1. The device detects its Component external working conditions The DC component in the AC Overhigh in real time. After the fault...
Page 97
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2062 Major Cause ID = 2 Send a shutdown command to Insulation devices connected to the same 1. The battery rack is short- Resistance DC bus.
Page 98
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2064 Device Major Cause ID = 3–12, 16, 17, 19 ● Cause ID = 3–12, 16, 17, 19 Fault Turn off the AC switch and...
Page 99
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2087 Internal Major Cause ID = 1–4 Turn off the AC switch and DC switch, wait for 5 minutes, and The internal fan is short-...
Page 100
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 2103 Major Cause ID = 1 Power off the devices Terminal connected to the same DC bus 1. The AC power cable is not...
Page 101
LUNA2000-100KTL-M1 Smart Power Control System User Manual 8 Alarm Reference Alarm Alarm Severi Possible Cause Suggestion Name 61440 Faulty Minor Cause ID = 1 Turn off the AC switch and DC Monitoring switch, wait for 5 minutes, and 1. The flash memory is...
LUNA2000-100KTL-M1 Smart Power Control System User Manual 9 Technical Data Technical Data Efficiency Technical Specifications LUNA2000-100KTL-M1 Maximum efficiency 98.40% DC Side Technical Specifications LUNA2000-100KTL-M1 Number of DC outputs Maximum DC voltage 1100 V Maximum DC power 123 kW Maximum DC current 215.8 A...
Page 103
LUNA2000-100KTL-M1 Smart Power Control System User Manual 9 Technical Data Technical Specifications LUNA2000-100KTL-M1 DC reverse polarity protection Supported DC surge protection Type II AC surge protection Type II Insulation resistance detection Supported Residue current monitoring unit Supported (RCMU) Overvoltage category...
Page 104
LUNA2000-100KTL-M1 Smart Power Control System User Manual 9 Technical Data Power Grid Technical Specifications LUNA2000-100KTL-M1 Rated AC voltage 380 V/400 V/440 V Rated AC power 100 kW Maximum apparent power 120 kVA Maximum active power 120 kW Rated AC current ●...
LUNA2000-100KTL-M1 Smart Power Control System User Manual A Crimping an OT or DT Terminal Crimping an OT or DT Terminal Requirements for OT/DT terminals ● If a copper cable is used, use copper wiring terminals. ● If a copper-clad aluminum cable is used, use copper wiring terminals.
Page 106
LUNA2000-100KTL-M1 Smart Power Control System User Manual A Crimping an OT or DT Terminal Figure A-1 Requirements for OT/DT terminals Crimping an OT or DT Terminal NO TICE ● Avoid scratching the core wire when stripping a cable. ● The cavity formed after the conductor crimp strip of the OT or DT terminal has been crimped must completely wrap around the core wires.
Page 107
LUNA2000-100KTL-M1 Smart Power Control System User Manual A Crimping an OT or DT Terminal Figure A-2 Crimping an OT terminal (1) Cable (2) Core (3) Heat-shrink tubing (4) OT terminal (5) Hydraulic pliers (6) Heat gun Figure A-3 Crimping a DT terminal...
LUNA2000-100KTL-M1 Smart Power Control System User Manual B Grid Codes Grid Codes NO TE The grid codes are subject to change. The listed codes are for reference only. Set the correct grid code based on the application area and scenario of the Smart PCS.
Page 109
LUNA2000-100KTL-M1 Smart Power Control System User Manual B Grid Codes Grid Code Description LUNA2000-100KTL-M1 Japan standard (60Hz) Japan standard power grid 2 Supported EN50438-TR Turkey low-voltage power grid Supported ANRE Romania low-voltage power Supported grid Japan standard (MV420-50Hz) Japan standard power grid...
LUNA2000-100KTL-M1 Smart Power Control System User Manual C Resetting Password Resetting Password Reset the password only when the AC power is supplied to the Smart PCS from the power grid, diesel generator, or other voltage-source PCSs. Step 1 Check that the AC and DC sides of the Smart PCS are both powered on, and indicators are steady green or blinking slowly for more than 3 minutes.
Preconfigured Huawei-issued certificates are used only in the deployment phase, for establishing initial security channels between devices and the customer's network. Huawei does not promise or guarantee the security of preconfigured certificates. The customer shall bear consequences of all security risks and security incidents arising from using preconfigured Huawei-issued certificates as service certificates.
LUNA2000-100KTL-M1 Smart Power Control System User Manual E Contact Information Contact Information If you have any questions about this product, please contact us. Table E-1 Customer service contact information Region Country Email Europe France eu_inverter_support@huaw 0080033888888 ei.com Germany Spain Italy...
LUNA2000-100KTL-M1 Smart Power Control System User Manual F Acronyms and Abbreviations Acronyms and Abbreviations smart string energy storage system fast ethernet gigabit ethernet light emitting diode RCMU residual current monitoring unit Smart PCS smart power control system Issue 02 (2023-01-10)