Toshiba RBP-RC001-E Installation & Owner's Manual page 26

Group remote controller
Table of Contents

Advertisement

RBP-RC001-E Installation & Owner's Manual
Changing the system operation settings
System operation screen
List of the setting items on the system operation screen
Item
Operate
Run
Mode
Cool PST
Heat PST
Demand
1
On the system information screen, press [ ] to display
the system operation screen.
2
Use [<] and [>] to select the item to change.
For information about how to set each item, refer to the table below.
3
To confirm the changes, press [ ] (Return) and on the
message screen, press [●] (Confirm).
Use [Λ] and [V] to switch between Link and Individual.
Use [Λ] and [V] to switch the current operating state.
*
If Operate is "Link", you cannot operate the system.
Use [Λ] and [V] to switch between Stop, Cool, and Heat.
*
If Operate is "Link", you cannot operate the system.
*
Changing the mode does not change the mode for the operation pattern.
Set the set temperatures for Cool/Heat.
Select either "C.PST" or "H.PST" and press [●] (Confirm) to display the set temperature input screen.
Use [<] and [>] to select an input digit, use [Λ] and [V] to change the value, and press [●] (Confirm).
The valid setting ranges are as in the table below.
Model
USX, EDGE Series
SFMC Series 4, 5
CAONS700
Heat Recovery CAONS
Series 1
Heat Recovery CAONS
Series 2
*
If you change the set temperature, the set temperature of the currently selected operation pattern is changed.
Set the demand current (for SFMC Series 4, 5, demand capacity).
Select "Demand" and press [●] (Confirm) to display the value input screen.
Use [<] and [>] to select an input digit, use [Λ] and [V] to change the value, and press [●] (Confirm).
The range of values that can be input is "0" to "30000".
*
The initial value is "0". Note that if you enable demand/power saving with an incorrect setting, the unit will be
stopped.
*
If you change the demand current and capacity, the demand current and capacity of the currently selected
operation pattern is changed.
Description
Cool PST [°C]
Initial
Setting range
value
7.0
4.0 to 30.0
7.0
5.0 to 25.0
30.0
9.0 to 35.0
26
32RCA001TS-02ISEN
Heat PST [°C]
Initial
Setting range
value
45.0
25.0 to 55.0
45.0
35.0 to 55.0
65.0
50.0 to 90.0
65.0
50.0 to 85.0
65.0
50.0 to 85.0

Advertisement

Table of Contents
loading

Table of Contents