5.1.3 Close the Door
- Excessive moisture or dust in the inverter could cause unexpected damage
due to the corrosion on the live part. Ensure the inner of the inverter clean
without unreasonable pollution is important for a lifetime operation system.
- After cabling or maintenance for the inverter, please lock both toggle latch to
make sure the inverter will remain IP66 protection.
1. Make sure that the terminals or viewable live parts are clean without sundries,
dust even liquid.
2. All protection covers are installed well.
3. Remove the hexagon wrench and close the door (Figure 5-2).
4. Buckle the latch lock as Figure 5-4-① and apply a brand new one-time-use
security seal (item 5, Table 2-1) on the toggle latch as Figure 5-4-②.
5. Fix the protection cover by the hexagon wrench as Figure 5-4-④.
6. The hexagon wrench can be fixed on the protection cover as Figure 5-4-⑤.
7. Fix the antenna with its bracket by 0.98 N-m torque.
- This inverter is compliant with the "Technical Specification for Security Inspection
of Solar Inverter and Monitoring Units" required by BSMI. After closing the door,
please apply a security seal on the toggle latch. We will not be liable or responsible
for any security incident caused by an improper application of the sticker.
ATTENTION
Figure 5-4: Close the door
ATTENTION
59
Maintenance
security seal