We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. This documentation is valid for the product PSS u2 ES 16DOD 0.5A hardware version 01 or higher. It is valid until new documentation is published.
Page 5
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSS u2 ES 16DOD 0.5A 1003616-EN-03...
Details of the terminal blocks that can be used are available under "Intended Use". Module features Application of the product PSS u2 ES 16DOD 0.5A: Electronic module with digital outputs and expanded diagnostics for standard applications The product has the following features: 16 Digital outputs –...
Use of the module outside the areas described in this manual, Any use of the module that is not in accordance with the technical details. The module PSS u2 ES 16DOD 0.5A may be used in conjunction with the following ter- minal block:...
Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.). 3.3.3 Disposal When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSS u2 ES 16DOD 0.5A 1003616-EN-03...
The value that is to be used as the substitute value can be configured. Substitute values may be: Output switched off (default value) Output switched on Last valid value Operating Manual PSS u2 ES 16DOD 0.5A 1003616-EN-03...
– The module switches off the voltage at the digital outputs. Standby mode – All module functions are inactive. – The LEDs for displaying the module and terminal status are switched off. Operating Manual PSS u2 ES 16DOD 0.5A | 10 1003616-EN-03...
Bit 4 Valid bit of output O4 Bit 5 Valid bit of output O5 Bit 6 Valid bit of output O6 Bit 7 Valid bit of output O7 Byte 1 Operating Manual PSS u2 ES 16DOD 0.5A | 11 1003616-EN-03...
Page 12
Valid bit of output O11 Bit 4 Valid bit of output O12 Bit 5 Valid bit of output O13 Bit 6 Valid bit of output O14 Bit 7 Valid bit of output O15 Operating Manual PSS u2 ES 16DOD 0.5A | 12 1003616-EN-03...
6.1.1 Dimensions The dimensions include the backplane, electronic module and terminal block. 12,5 51,1 111,1 Fig.: Dimensions in mm, including backplane, electronic module and terminal block Operating Manual PSS u2 ES 16DOD 0.5A | 13 1003616-EN-03...
Unforeseeable error reactions may be triggered if modules are inserted and removed under load. 6.2.1 Inserting an electronic module 1. Insert the electronic module into the suspen- sion lug on the back- plane. Operating Manual PSS u2 ES 16DOD 0.5A | 14 1003616-EN-03...
Page 15
3. Insert the terminal block into the suspen- sion lug on the module. 4. Swivel the terminal block upwards until you hear it click into place. Operating Manual PSS u2 ES 16DOD 0.5A | 15 1003616-EN-03...
2. Press the unlocking mechanism that is shown by the arrow and pull off the electronic module upwards. Operating Manual PSS u2 ES 16DOD 0.5A | 16 1003616-EN-03...
– Restart of the head module. After a restart, the system behaves as after a warm reset using a reset pushbutton (see operating manual of the head module, chapter “Reset pusbutton", section "Carrying out a warm reset (restart)"). Operating Manual PSS u2 ES 16DOD 0.5A | 17 1003616-EN-03...
The minimum cable cross section for field connection terminals on the terminal blocks is 0.15 mm (AWG26). The maximum cable cross section for field connection terminals on the terminal blocks is 1.5 mm with ferrules (AWG14) Use copper wiring. Operating Manual PSS u2 ES 16DOD 0.5A | 18 1003616-EN-03...
The module status display See module's dia- and the terminal status display gnostic log on the relevant output flash synchronously Short circuit/overload/under- voltage Temperature warning: Too See module's dia- warm (1) gnostic log Operating Manual PSS u2 ES 16DOD 0.5A | 20 1003616-EN-03...
Page 21
After the "too hot" message has been received, if the temperature drops back below the "too warm" threshold value, the module will switch to an error-free state. Legend LED on LED flashes LED flashes briefly LED off Operating Manual PSS u2 ES 16DOD 0.5A | 21 1003616-EN-03...
In accordance with the standard EN 60068-2-1/-2 Temperature range -40 - 70 °C Climatic suitability In accordance with the standard EN 60068-2-78 Humidity 93 % r. h. at 40 °C Operating Manual PSS u2 ES 16DOD 0.5A | 22 1003616-EN-03...
Page 23
Mechanical data Material Housing Mounting type plug-in Dimensions Height 110,8 mm Width 12,5 mm Depth 72,5 mm Weight 36 g Where standards are undated, the 2015-04 latest editions shall apply. Operating Manual PSS u2 ES 16DOD 0.5A | 23 1003616-EN-03...
Label holder for terminal block 328912 (10 pcs.) 61 x 11.5 mm, scope of supply: 10 pieces Codierelemente Produkttyp Merkmale Bestell-Nr. PSS u2 A CE E (10 pc.) Codierelemente für Elektronikmodule, 10 328860 Stück Operating Manual PSS u2 ES 16DOD 0.5A | 24 1003616-EN-03...
Page 25
Order reference Backplanes Product type Features Order no. PSS u2 B 1 Backplane, 1 slot 328811 PSS u2 B 4 Backplane, 4 slots 328810 Operating Manual PSS u2 ES 16DOD 0.5A | 25 1003616-EN-03...
Page 26
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...