Download Print this page

enphase M215 Instructions Manual page 7

Hide thumbs Also See for M215:

Advertisement

Energize the System
12
a. If applicable, turn ON the AC disconnect or circuit
breaker for the branch circuit.
b. Turn ON the main utility-grid AC circuit breaker.
Your system will start producing power after a
five-minute wait time.
13
Use the Envoy to Complete System Setup
Refer to the to the Envoy Quick Install Guide for
details on the following steps:
a. An automatic device scan runs for eight hours af-
ter the Envoy is installed. If this scan has expired,
start a new scan:
• Press and hold the Envoy menu button (on the
right side of the Envoy).
• Release the menu button when the LCD screen
displays Enable Device Scan.
b. Use the Envoy menu button
to select Enable Commu-
nication Check. Ensure at
least three level bars show
on the LCD.
c. When all devices are de-
tected, stop the scan. To do
this, use the Envoy menu
button to select Disable
Device Scan.
Envoy menu
button
(rear view)
Enphase Energy, Inc.
1420 N. McDowell Blvd.
Petaluma, CA 94954
USA
info@enphaseenergy.com
http://www.enphase.com
Step Details
3
NOTE: Verify that AC voltage at the site is within range:
240 Volt AC Single-Phase
L1 to L2
211 to 264 VAC
L1, L2, to N
106 to 132 VAC
WARNING: Only use electrical system components approved
for wet locations.
WARNING: Do not exceed the maximum number of microin-
verters in an AC branch circuit as listed in the table below. Each
branch circuit must be protected by a dedicated circuit breaker
of 20 A or less.
Service type
240 VAC single-phase
208 VAC three-phase
WARNING: Size the AC wire gauge to account for voltage drop
for both the branch circuit and all upstream conductors lead-
ing back to the PCC. See Circuit Calculations for M215 at
http://www.enphase.com/support.
4
DANGER: ELECTRIC SHOCK HAZARD. THE DC
CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE ENERGIZED.
WARNING: Allow a minimum of 1.9 cm (0.75") between the
roof and the microinverter. Also allow 1.3 cm (0.50") between
the back of the PV module and the top of the microinverter.
NOTE: Torque the microinverter fasteners to the values shown.
Do not over torque:
• 1/4" mounting hardware – 5 N m (45-50 in-lbs)
• 5/16" mounting hardware – 9 N m (80-85 in-lbs)
Using a power screwdriver is not recommended due to the risk
of thread galling.
NOTE: The AC output neutral is not bonded to ground inside
the  microinverter.
6
WARNING: Install sealing caps on all unused AC connectors
as these become live when the system is
energized by the utility. The IP67-rated
sealing caps are required for
protection against moisture ingress.
NOTE: To remove a sealing cap, you
must use the Enphase disconnect tool or
a #3 Phillips screwdriver.
8
NOTE: The Engage Cable uses the following wiring scheme.
240 Volt AC Single-Phase Wires
Black – L1
Red – L2
White – Neutral
Green – Ground
NOTE: The green wire acts as equipment ground (EGC).
© 2014 Enphase Energy Inc. All rights reserved.
208 Volt AC Three-Phase
L1 to L2 to L3
183 to 229 VAC
L1, L2, L3 to N
106 to 132 VAC
Max M215s per branch
17
25
disconnect
tool
208 Volt AC Three-Phase Wires
Black – L1
Red – L2
Blue – L3
White – Neutral
Green – Ground

Advertisement

loading

This manual is also suitable for:

M215-60-2ll-s22-igM215-60-2ll-s23-igM215-60-2ll-s24-ig