Appendix: List of DIP switch settings
The following table illustrates the
Configuring the CBV-2U4-3T(-N) for BACnet communications
Note:
If the
DIP
switch is set to all zeros, the device will retain the address to which it was last set, but that address
can be subsequently overridden by software.
If no address had previously been set (e.g. when the device is received from the factory), then a device that is
powered-on with the
address.
0000001
0000010
Address 1
Address 2
0001001
0001010
Address 9
Address 10
0010001
0010010
Address 17
Address 18
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Appendix: List of DIP switch settings
CBV-2U4-3T(-N) |
DIP
switch settings for all possible controller MSTP address settings. See
0000000
Software Selectable
DIP
switch set to all zeros will use the last 2 digits of its serial number as its initial
0000011
0000100
Address 3
Address 4
0001011
0001100
Address 11
Address 12
0010011
0010100
Address 19
Address 20
on page 18 for more details.
0000101
0000110
Address 5
Address 6
0001101
0001110
Address 13
Address 14
0010101
0010110
Address 21
Address 22
0000111
0001000
Address 7
Address 8
0001111
0010000
Address 15
Address 16
0010111
0011000
Address 23
Address 24
71