ABB CBV-2U4-3T User Manual page 65

Table of Contents

Advertisement

CBV-2U4-3T(-N) |
POINT SETPOINT
OBJECTNAME
BLOCK
208
No
PriAirModeEnumeration (A208)
210
Yes
TABPriAirDbandStpt (A210)
211
Yes
TABPriAirMaxStpt (A211)
212
Yes
TabPriAirMaxHgtStpt (A212)
214
Yes
Fusion_Offset(A214) with Actuator
215
KFactorOut (A215)
216
Yes
Fusion_StptStepSize (A216) with
Actuator
218
Yes
MeasuredFlow/K (A218)
219
No
PriDamperCmdEnumeration (A219)
221
Yes
CBT_STAT_CFG (A221)
224
Yes
TABFanDbandStpt (A224)
225
Yes
TABFanMaxStpt (A225)
226
Yes
TABFanHtgMaxStpt (A226)
227
Yes
TABFanStandbyStpt (A227)
230
Yes
UI01_10KSensorCal (A230)
231
Yes
SetptSliderSpan (A231)
232
Yes
ZonePIDGain (A232)
235
Yes
HeatStateOffStpt (A235)
236
Yes
PriAirPIDGain (A236) with Actuator
236
Yes
PriAirPIDGain (A236) without Actuator
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Appendix : List of CBV-2U4-3T(-N) points
DESCRIPTION
during unoccupied mode. (FA
Variants only)
Numerated value of primary air mode
state.
0 = On
1 = Off
3 = Fire stop
Primary air control dead band
Flowrate setpoint. This point
supports priority array.
Primary air maximum Flowrate
setpoint. This point supports priority
array.
Primary air max heating Flowrate
setpoint. This point supports priority
array.
The maximum adjustment of the
setpoint range for the FusionAir
sensor. (FA Variants only)
Displays the current calculated K-
factor
The amount of degrees the setpoint
is adjusted with every button press
on the FusionAir sensor. (FA Variants
only)
When KFactSelect (D204) is True,
input measured flow from balancer.
When KfactSelect (D204) is False,
input factory K-factor
Enumerated value for damper
command state
0 = Off
1 = Open
2 = Close
4 = Close Flowrate high for series fan
8 = Open manual
16 = Close manual
32 = Closed fire stop
Enumerated value for CBT-Stat
operation
0-None
1-OccOvrd
2-Temp Setpoint Adj
3-OccOvrd & Temp Setpoint Adj
4-Perm Setpnt Adj
5-OccOvrd & Perm Setpnt Adj
Minimum variable fan speed
command setpoint
Maximum cooling variable speed fan
command setpoint
Maximum heating variable speed fan
command setpoint
Variable fan speed command
setpoint when in standby mode
UI01 calibration offset
Setpoint slider span
Zone temperature PID gain
Temperature setpoint for setting
Primary Air State to cold when VAV
box has been configured for local
auto change over.
Primary air PID gain
Primary air PID gain
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
0
no-units
0
no-units
50
CFM
25
l/sec
800
CFM
400
l/sec
50
CFM
25
l/sec
5
°F
5
°c
CFM@1"
l/sec@1Pa
.5
°F
.5.
°c
0
no-units
0
no-units
no-units
no-units
3
3
0
%
0
%
60
%
60
%
60
%
60
%
0
%
0
%
0
°F
0
°c
4
°F
4
°c
10
no-units
10
no-units
72
°F
21
°c
0.11
no-units
0.11
no-units
no-units
no-units
0.10
0.10
65