For UI1 Configuration, set
0 = Local Zone Temp Only (default)
2 = Local Zone Temp w/ Override Button
3 = Spare Temp or Dig In – Use Remote Zone Temp
For UI2 Configuration, set
0 = None or Spare Temp or Spare Dig In
12 = 5K Stpt Slide Adjust
For UI3 Configuration, set
0 = Discharge Air Temperature (default)
For UI4 Configuration, set
0 = None / Remote CO2 / Dehumidifier
32 = Local CO2
For UI4 Configuration, set
2 = Local Dehumidifier
1 = Local OCC Sensor
5 = Spare Digital Input
For the Primary State Options, set InputConfigA(A242) analog setpoint to the following:
0 = Switch Heat/Cool Primary Air State by Master Control
16 = Switch Heat/Cool Primary Air State by Supply Air Temperature
Note: To configure multiple UI settings, add numbers together for InputConfigA(A242). For example, to set UI1 for
Local Zone Temp w/Override Button and UI2 with the 5K Stpt Slide adjust, InpugConfigA(A242) will be set to
14.