ABB CBV-2U4-3T User Manual page 27

Table of Contents

Advertisement

AO Range Configuration
AO14
0 = AO14 is 0-10 VDC – AOConfigD(A286)
1 = AO14 is 2-10 VDC – AOConfigD(A286)
2 = AO14 is custom open and closed voltage – AOConfigD(A286)
AO14 Voltage
0 = AO14 is direct acting - AOConfigD(A286)
4 = AO14 is reverse acting - AOConfigD(A286)
AO15
0 = AO15 is 0-10 VDC - AOConfigD(A286)
8 = AO15 is 2-10 VDC - AOConfigD(A286)
16 = AO15 enter custom open and closed voltage - AOConfigD(A286)
AO15 Voltage
0 = AO15 is direct acting - AOConfigD(A286)
32 = AO15 is reverse acting - AOConfigD(A286)
Note: To configure multiple output settings, add numbers together for AOConfigD(A286). For example, set AO14 to
2-10 VDC and AO15 to reverse acting, AOConfigD(A286) will be set to 33.