ABB CBV-2U4-3T User Manual page 67

Table of Contents

Advertisement

CBV-2U4-3T(-N) |
327
No
SysMode (A327)
334
Yes
netOCC (A334)
369
Yes
TriStateHtVlvMinOnTime (A369)
371
Yes
DegreesAbvBlwSPAlarm (A371)
373
Yes
TempAlarmOnDelay (A373)
379
Yes
CFMAlarmOnDelay (A379)
380
Yes
TABParallelDisableFanSP (A380)
381
Yes
TABParallelFanDB (A381)
383
Yes
SeriesFanStartLckOutSP (A383)
385
Yes
SliderValAt_N2 (A385)
386
Yes
SliderValAt_N1 (A386)
387
Yes
SliderValAt_0 (A387)
388
Yes
SliderValAt_P1 (A388)
389
Yes
SliderValAt_P2 (A389)
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Appendix : List of CBV-2U4-3T(-N) points
Enumerated value for System Mode
state:
0 = DB
1 = Heat
2 = Cool
Enumerated value for Aspect
Schedule Point netOCC:
0 = Vacant
1 = Warmup
2 = Occupied
3 = Setback
Tristate valve minimum on time in
seconds
Zone temperature error from current
temperature setpoints alarm
Amount of minutes before zone
temperature alarms are triggered
Amount of minutes before Flowrate
alarms are triggered
Parallel fan is enabled when Flowrate
is below this setpoint
Parallel fan will be disabled when
Flowrate is above this point +
TABParallelDisableFanSP (A380)
Series fan is disabled if Flowrate is
above this setpoint when first
energized. If this occurs, damper will
drive shut and when Flowrate drops
below this setpoint series fan will
start
Resistance at
UI02
when slider is all
the way to the left
Resistance at
UI02
when slider is
between all the way to left and
middle
Resistance at
UI02
when slider is in
middle
Resistance at
UI02
when slider is
between all the way to right and
middle
Resistance at
UI02
when slider is all
the way to the right
no-units
no-units
0
0
no-units
no-units
2
2
2
sec
2
sec
2
°F
2
°C
60
min
60
min
30
min
30
min
3000
cfm
1500
l/sec
50
cfm
25
l/sec
200
cfm
100
l/sec
15
ohms
15
ohms
1315
ohms
1315
ohms
2800
ohms
2800
ohms
4460
ohms
4460
ohms
4989
ohms
4989
ohms
67