Output Configuration
DO11
•
0 = None
•
7 = Heat 1 On/Off - OutputConfigA(A243)
•
64 = TriState 11 Open/12 Close – OutputConfigB(A261)
•
3 = Heat 1 PWM – OutputConfigA(A243)
DO12
•
0 = None
•
56 = Heat 2 On/Off - OutputConfigA(A243)
•
0 = TriState 11 Open/12 Close (set at DO11)
•
24 = Heat 2 PWM - OutputConfigA(A243)
DO13
•
0 = None
•
64 = Parallel Constant Volume Fan
•
-64 = Series Constant Volume Fan
•
Heat 3 On/Off OutputConfigA(A243) = 192, OutputConfigB(A261) = 128
•
192 = Heat 3 PWM
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Installation Overview
CBV-2U4-3T(-N) |
24