Custom Energy Savings Settings
15 – MAXIMUM SETBACK TEMPERATURE
72-92
(78°F* default setting) Select the "Maximum Setback Temperature" in
°F.
Setback temperature is calculated by measuring PTAC unit's ability to
attain "Recovery Temperature - Cool" within "Temperature Recovery
Time".
If recovery is disabled ("Temperature Recovery Time" is set to "0") or
if setback temperatures have not yet been calculated, the "Maximum
Setback Temperature" value will be used as the setback temperature for
cooling.
If calculated setback temperature for air conditioning is higher than
"Maximum Setback Temperature", then the "Maximum Setback
Temperature" will be used as setback temperature for air conditioning.
This feature allows defi ning the maximum temperature in a room when
room is unoccupied and the thermostat is in the setback mode.