Incidental Occupancy Threshold - Emerson VERDANT VX Series Installation Manual

Wired energy management thermostat with an occupancy sensor
Table of Contents

Advertisement

Custom Energy Savings Settings
05 – INCIDENTAL OCCUPANCY THRESHOLD
00-60
(05* default setting) Select the minimum period of time (in minutes) for
which occupancy needs to be detected to enter the guest occupancy
mode.
When occupancy is detected, thermostat will switch to occupied mode
for a duration of "Incidental Occupancy Threshold" selected here.
If occupancy is detected for a period of time shorter than the "Incidental
Occupancy Threshold" selected here, the thermostat will automatically
revert to unoccupied mode at the end of the "Incidental Occupancy
Threshold" period and continue to observe energy saving functions that
were in effect before the room became occupied. This setting allows
ignoring incidental room visits.
If occupancy is detected for a period of time longer than the "Incidental
Occupancy Threshold" selected here, the thermostat will enter the
guest occupancy mode. When the thermostat is in the guest occupancy
mode, it will revert to unoccupied mode and initiate the setback
temperature only when occupancy is not detected for the duration of
the setback delay (Heat or Cool) period.