Electrical Connection - Grundfos MULTILIFT MD1 Installation And Operating Instructions Manual

Hide thumbs Also See for MULTILIFT MD1:
Table of Contents

Advertisement

4.2.5 Installing a diaphragm pump
Make sure that the weight from the inlet,
outlet and vent pipes does not rest on the
tank. Long pipe sections and valves must
be supported.
You can use the optional, manually operated
diaphragm pump for draining the tank before service
or maintenance. To enable service or maintenance,
we recommend that you fit an isolating valve. The
tank has two outlets for 1 1/4" and 1 1/2" pipes. The
flexible connecting piece for 1 1/2" is supplied with
the lifting station.
1. Drill the outlet port with a 20 mm drill.
It is necessary to drill the outlet as it may have
been filled with tank material during the moulding
process.
2. Connect the outlet to the pipe for the diaphragm
pump by means of the flexible connecting piece
and hose clamps.
3. Connect the diaphragm pump to the collecting
line.
The outlet pipe of the diaphragm pump must have
a bend above the backflow level which is often the
street level. Ask your local authorities.

4.3 Electrical connection

WARNING
Electric shock
Death or serious personal injury
Switch off the power supply before you
start any work on the product. Make
sure that the power supply cannot be
switched on accidentally.
Lock the main switch in off position, or
unplug the power plug. Type and
requirements are specified in EN
60204-1, 5.3.
WARNING
Electric shock
Death or serious personal injury
The protective earth (PE) of the power
outlet must be connected to the
protective earth of the product. The
plug must have the same PE
connection system as the power outlet.
WARNING
Electric shock
Death or serious personal injury
The installation must be fitted with a
residual current device (RCD) with a
tripping current less than 30 mA.
WARNING
Electric shock
Death or serious personal injury
The product must be connected to an
external main switch with a minimum
contact gap of 3 mm (0.12 inch) in all
poles.
WARNING
Electric shock
Death or serious personal injury
Before opening the control cabinet,
switch off the power supply.
The operating voltage and frequency are marked
on the controller nameplate. Make sure that the
controller is suitable for the power supply on
which it will be used.
All cables/wires must be fitted through the cable
entries and gaskets.
If required according to local regulations, install an
external main switch.
15