5 Installation at Site
5.1 Safety regulations
DANGER
Incorrect installation
Danger to life!
▷ The control unit must be installed in a flood-proof location.
▷ Never install the control unit in potentially explosive atmospheres.
▷ Do not use the control unit for controlling pumps in potentially explosive
atmospheres.
▷ For integration in an external control system observe the directives for low-
voltage switchgear and controlgear assemblies.
5.2 Checks to be carried out prior to installation
Before beginning with the installation check the following:
▪ The place of installation is dry.
▪ The place of installation is frost-free.
▪ The place of installation is protected against flooding.
▪ The place of installation is well-ventilated.
▪ The place of installation is not potentially explosive.
▪ The specified ambient conditions are met.
Table 7: Ambient conditions
Characteristic
Temperature during operation
Relative humidity
Installation altitude
5.3 Installing the control unit
The control unit must be handled with care to prevent damage to the components.
ü The place of installation meets the requirements indicated.
1. Remove the control unit from its original packaging.
2. Install the control unit on a stable base (e.g. wall, bracket, etc.).
MSE/MSD
Value
-10 °C to +50 °C
Non-condensing
1000 m above MSL (max.)