Setting the level-dependent control.................... 14 Commissioning/Start-up/Shutdown.................... 15 Prerequisites for commissioning/start-up...................... 15 Start-up ................................ 15 Shutdown................................ 16 Returning to service ............................ 16 Maintenance............................ 17 Trouble-shooting.......................... 18 Related Documents .......................... 19 Wiring diagram............................... 19 EU Declaration of Conformity ...................... 20 Index .............................. 21 MSE/MSD 3 of 24...
The serial number uniquely describes the product and is used as identification in all further business processes. In the event of damage, immediately contact your nearest KSB service facility to maintain the right to claim under warranty. 1.2 Target group This operating manual is aimed at the target group of trained and qualified specialist technical personnel.
In conjunction with one of the signal words this symbol indicates a hazard involving electrical voltage and identifies information about protection against electrical voltage. Machine damage In conjunction with the signal word CAUTION this symbol indicates a hazard for the machine and its functions. MSE/MSD 5 of 24...
– Hazards to persons due to electrical, thermal, mechanical and chemical effects and explosions – Failure of important product functions – Failure of prescribed maintenance and servicing practices – Hazard to the environment due to leakage of hazardous substances MSE/MSD 6 of 24...
In addition to the safety information contained in this operating manual and the intended use, the following safety regulations shall be complied with: ▪ Accident prevention, health regulations and safety regulations ▪ Explosion protection regulations ▪ Safety regulations for handling hazardous substances ▪ Applicable standards, directives and laws MSE/MSD 7 of 24...
1. On transfer of goods, check each packaging unit for damage. 2. In the event of in-transit damage, assess the exact damage, document it and notify KSB or the supplying dealer and the insurer about the damage in writing immediately.
NOTE Due to certain components it contains, the device is classified as special waste and meets RoHs 2011/65/EC requirements. Once decommissioned, the device must be properly disposed of in accordance with local regulations. MSE/MSD 9 of 24...
Motor Protection relay Single-phase alternating current Three-phase current Max. amperage x 10 Code number 4.4 Name plate KSB SE & Co. KGaA Johann-Klein-Straße 9 67227 Frankenthal Deutschland MSD 60.1 LevelControl Basic 2 3/N/PE AC 400 V 50 Hz 1/N AC 230 V 50 Hz...
Design ▪ Control unit ▪ Level-dependent control ▪ Protection of a pump with single-phase AC motor (MSE) or three-phase motor (MSD) ▪ The pump is started and stopped as a function of the fill level. ▪ Level measurement via float switch ▪...
The control unit must be handled with care to prevent damage to the components. ü The place of installation meets the requirements indicated. 1. Remove the control unit from its original packaging. 2. Install the control unit on a stable base (e.g. wall, bracket, etc.). MSE/MSD 12 of 24...
4. Set the motor protection relay to the rated current. 5. For three-phase motors, connect the power cable available on site so as to ensure a clockwise rotating field. 6. For single-phase AC motors, ensure that phase and neutral are connected correctly. MSE/MSD 13 of 24...
2. Observe the required free cable length of the float switch. 3. The minimum free float switch cable length measured from the antikink bush is 10 cm. 4. Fasten the float switch cable with suitable fasteners. MSE/MSD 14 of 24...
5. To establish the power supply connect the control unit and set the site-supplied safety device to ON. 6. If three-phase motors are used, check the direction of rotation. ð To do so, briefly set the manual-0-automatic selector switch to manual. 7. Set the manual-0-automatic selector switch to automatic. MSE/MSD 15 of 24...
4. Prior to any work on the control cabinet, use a voltmeter to verify that all phases are dead. 6.4 Returning to service For returning the equipment to service, observe the sections on commissioning/start- up . MSE/MSD 16 of 24...
- Phase failure Check power cable. ✘ Float switch is stuck. Release and check for free movement. ✘ Incorrect pump selection Have it checked by KSB Service. ✘ Manual-0-automatic selector switch is set to Set the manual-0-automatic selector switch to manual. automatic.
9 Related Documents 9 Related Documents 9.1 Wiring diagram To connect the pump and float switch, refer to the enclosed circuit diagrams. MSE/MSD 19 of 24...
10 EU Declaration of Conformity 10 EU Declaration of Conformity Manufacturer: KSB SE & Co. KGaA Johann-Klein-Straße 9 67227 Frankenthal (Germany) The manufacturer herewith declares that the product: MSE / MSD Serial number range: 2022w01 to 2024w52 ▪ is in conformity with the provisions of the following directives / regulations as amended from time to time: –...