Levelflex FMP53 FOUNDATION Fieldbus
Endress+Hauser
12.8.3
Configurable area
The event category can be individually defined for the following events - irrespective of the
event group they are assigned to in the default setting:
• F941: Lost echo
• S942: In safety distance
To change the event category, the event first has to be assigned to one of the bits 1 to 15.
The FF912 ConfigArea_1 to FF912ConfigArea_15 parameters in the DIAGNOSTIC
(TRDDIAG) Block are used for this purpose. Then the corresponding bit can be set from 0
to 1 in the desired assignment parameter.
Example
Error 942 "In safety distance" should no longer be categorized as Out of specification (S)
and should be categorized as Function check (C) instead.
1.
In the FieldCare navigation window, navigate to Expert → Communication → Field
diagnostics → Alarm detection enable.
2.
In the default setting, all bits in the Configurable Area Bits column have the value
not used.
3.
Select one of these bits (here for example: Configurable Area Bit 1) and select the In
safety distance option from the corresponding selection list. Press Enter to confirm
the option selected.
Commissioning (block-oriented operation)
91