17 Essential Setup Procedures

17.1 The Entry Code

1)
Press SETUP on the control panel.
2)
Use the arrow keys on the control panel to change the value displayed. If you
change the code do not forget it.
3)
Press SETUP again.

17.2 Set the Time and Date

1)
Use the down arrow until SET CLOCK is on the top line of the display.
2)
Press SETUP. The cursor shows which line you will change.
3)
Use the down arrow to change NO to YES.
4)
Press SETUP.
5)
Use the arrow keys to change the day.
6)
Press SETUP to confirm.
To change the time use the arrow keys and press SETUP to confirm. (A 24
hour clock is used.)

17.3 Set the Alarm Levels

ALARM A
1)
Select the required alarm with the down arrow.
2)
Press SETUP.
3)
Use the arrows to change the value, zero to 4000 in steps of 10. Press SETUP
to confirm.
4)
Repeat for the midpoint alarms, MID AL A.

17.4 Selecting an appropriate alarm level.

There is no right or wrong level, each application must be considered in isolation.
Use the monitor to assess normal operating levels and then set the alarm levels at
an appropriate margin above normal levels so as not to cause false alarms whilst
still providing adequate protection. The output signals from the monitor must be
considered as data for evaluation by operating staff rather than simple go / no go
alarms.

17.5 Select the Units of Measurement

User Guide
ENTRY CODE
The entry code is factory set to 4.
_ALARM A:
OP1 MIN:
0
The line you wish to
change must be at the
nnn ppm
TOP of the screen. Edit
mode is indicated by
the cursor.