5.1
Understanding requirements for the fresh-water system
10
1" Pump
Inlet Strainer
(40 mesh)
Lower Bowl Water
Supply Line
Freshwater
Holding Tank
General guidelines
Follow all applicable local and national regulations, codes, and standards
All water supply system plumbing should be 1" ID with a recommended 100 PSI minimum
working pressure rating
Water inlet strainer: 1" ID, 40 mesh
Pressure gauge: 0 – 100 PSI
Water pump guidelines
Grundfos MQ3-35 or equivalent is recommended
1" NPT connections
Internal pressure switch: 50 PSI cut-out, 30 PSI cut-in
MQ3 Pump draw: 8 A @110 V, 4 A @ 220 V (pumps vary by manufacturer)
15 gpm required (MQ3 pump rated at 22 GPM max flow with no restrictions)
Choose a pump with adequate suction lift capability for pump installation parameters (MQ3
pump has 25' of suction life capability, but varies depending on horizontal run)
Potable water pressure (accumulator) tank guidelines
Amtrol Well-X-Trol WX-105-PS or equivalent is recommended
3/4" NPT, or larger connections
5 gallon total volume, 1.8 gallon drawdown @ 30/50 PSI
Air pressure charge: 2-4 PSI below pump cut-in pressure
Recommended to use one five-gallon accumulator tank for up to six heads
Pressure relief valve guidelines
I
Installation of a pressure relief valve is recommended by the accumulator tank
manufacturer in order to protect the fresh water system in case of pressure switch
malfunction.
Install near accumulator tank and pump
Set to open at excessive water system pressures
9
Pressure
Gauge
(0–100 PSI)
Check
High-flow
Valve
Water Pump
Fresh Water To
Other Fixtures
5-Gallon
Switch/Status Panel
Potable Water
Pressure Tank
Rim Water
(30/50 PSI)
Supply Line
Maintenance
Ball Valve
Blackwater
Holding Tank
Toilets
Toilet
Electric High-flow
Water Jet Valve
Check
Valve
EN