Safety Instructions; Troubleshooting; Safety Certification - FILL-RITE FR100 Series Installation And Operation Manual

Rotary hand pump
Table of Contents

Advertisement

Available languages

Available languages

|
FR110, FR112, FR112C, FR112CL & FR113 Pumps
FR112
WARNING
The FR100 Series hand pump shall not be
used to pump fuel into any type of aircraft!
WARNING
The FR100 Series hand pump is not suitable to
pump fluids for human consumption, or
fluids containing water.
Fluid Compatibility
Compatible Fluids
Gasoline, Diesel, Heptane, Kerosene,
Stoddard Solvents, Light Oils, Mineral Spirits
(Okay to pump)
Water, Sulfuric Acid, Naptha, Methanol,
Non-Compatible Fluids
Methyl Ethyl Ketone (MEK), Acetone, Ammonia,
(DO NOT pump)

Safety Instructions

To ensure safe and efficient operation, it is essential to read and follow each of these
warnings and precautions:
1. Improper use or installation of this product can cause serious bodily injury or death.
2. Do NOT smoke near pump or use pump near an open flame when pumping
flammable fluids. Fire could result.
3. A Fill-Rite filter should be used on pump outlet to ensure that no foreign material
is transferred to fuel tank.
4. Use gasoline and oil resistant thread sealant or sealant tape on all threaded
joints to protect against leakage.
5. Storage tank or barrel should be anchored to prevent tipping in both the full and
empty conditions.
6. To minimize static electricity build-up, keep nozzle in contact with container
being filled.
7. Regardless of mounting style, all tanks must be properly vented.
Thank You!
Thank you for purchasing the FR100 Series Rotary Hand Pump! Your Fill-Rite
uct comes with over 55 years of pump manufacturing experience behind it, providing
you the value that comes with superior performance, user-friendly design, outstanding
durability, and solid, simple engineering.
fillrite.com
FR100 SERIES ROTARY HAND PUMP
FR112C
FR113
Benzene, Bleach, Chlorine
prod-
®
INSTALLATION AND OPERATION MANUAL
Pump Installation
NOTICE
All pipe threads must have a sealant to protect
against leaks. Use sealant tape provided with
this pump, or use a gasoline and oil resistant
pipe sealant.
1. Screw suction pipe into pump inlet flange and tighten.
2. Extend suction pipe into tank or barrel opening to within 3" of bottom of tank or
barrel. Do not rest suction pipe on bottom.
3. Screw inlet flange of pump completely and securely into undamaged tank
or barrel bung.
Pumps with Hoses and Nozzles
4. Screw one end of hose into pump discharge opening and the nozzle to
the other end of hose.
Pumps with Discharge Spouts
4. Screw discharge spout assembly into top of pump.
Pumps with Meter, Hose, and Nozzle
4. Screw street elbow into top of pump, nipple into street elbow, meter onto nipple.
NOTE: Position the meter to the right of the handle facing operator for ease of
operator viewing. Screw one end of hose into meter outlet and the nozzle to the
other end of hose.
Installation of Counter
1. Remove crank from shaft.
2. Remove two screws directly above horizontal centerline of pump.
Push drive gear onto shaft with flat in gear hole located on longer flat of shaft.
3. Position counter on pump and attach with two screws and two washers.
4. Reattach crank.

Troubleshooting

If Pump Fails to Prime: Check suction line for leaks or obstructions.
Check vanes and slots for nicks, burrs, or wear. Check rotor for excessive wear or damage.
Low Pumping Capacity: Remove and clean screen. Check for leaks in suction line.
Check rotor and vanes for excessive wear and damage. Check for dirty filter on outlet side.
Pump Fluid Leakage: Clean O-ring seal and seat area. Replace seal. Replace vacuum
breaker. Tighten covers and joints. Check for dirty filter on outlet side.

Safety Certification

2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr110Fr112Fr112cFr113

Table of Contents