5. MAINTENANCE

5.5 Filter

If the filters are equipped with a pressure transducer the control panel automatically gives an
alarm when the filters have to be changed. Still every 6 month the filters should be checked
for damage/leakages which will not be detected by the pressure transmitter. If no pressure
transmitter is installed the following steps should be taken every 6 month:
Check the filter for dirt and damage.
Measure the pressure loss over the filter which should not be below 150 Pa (G3/G4)
or 250 Pa (F5/F7). If the pressure loss is higher the filters have to be changed.
Open the filter rail by the blue handles (1).
Take out the filters (2) and check the gasket on the filter rail for damage.
Clean the filter rail and reinstall the old/new filters.
5.6 Heating coil
The following steps should be taken to maintain the heating coil:
Check the coils for dust or dirt. If necessary, clean the aluminium fins by a soft brush
or a vacuum cleaner.
Straighten any bent slats using appropriate tools
Air the coil circuits through the exhaust valves of the pipe system (air in the pipe
system may reduce the capacity)
Check that the frost sensor is properly fixed.

5.7 Cross flow heat exchanger

The cross flow heat exchanger has no mechanical part, therefore only the plates should be
checked and cleaned if necessary. Clean the plates with a soft brush or use high pressure
cleaner with compressed air and blow against the air stream.
32